Specifications
47
Function Block for Siemens 115 U Section 5-10
A write-access to these data types is principally carried out with a coordination flag.
Just like the communications block, the coordination flag must be defined such that
the settings in the terminal and passive device are in agreement.
Part of a program installed in the receiving device, denoted in the PLC as data
handling block, will monitor the coordination flag.
If the coordination flag is set, the data will be processed by the data handling block
in accordance with the first 4 bytes in the communications block.
After the data have been processed, the coordination flag will be erased thereby
allowing further transmissions.
5.9 Protocol 3964R - Restrictions
The protocol 3964 allows data comprising a maximum of 128 bytes to be transmit-
ted per message. No further messages are transmitted or processed.
5.10 Function Block for Siemens 115 U
The supplied function block FB186 can be implemented in a Siemens 115 U.
The function block processes data from the terminal which are to be transmitted to
the PLC.
The first 4 bytes of the data which are written to the defined communications data
block are interpreted in accordance with the table ”Assignment of Bytes 1-4”.
The function block FB186 supports the following commands from the table ”As-
signments of Bytes 1-4”:
2 Output Byte
3 Flag Byte
11 Output Bit
12 Flag Bit.
When activating the function block, the communications data block and the coor-
dination flag must be specified as parameter. These parameters must comply with
the settings in the terminal.
The defined communications data block must comprise a size of 128 bytes or 64
data words, respectively.