User's Manual

Power Safety
Protect 8.33
Industrial High Power UPS
Complete Systems
Protect 8. is a true on-line double conversion UPS classified as
VFI SS 111 according to IEC 62040-3.
On-line operation ensures permanent service
Microprocessor-driven control and command system
provides reliable power supply
Battery management system boosts battery life and cuts
operating costs
Broad range of output power ratings, battery autonomy
times and options meet complex industrial applications
needs
High level protection for users and connected equipment
(high intermittent overload capacity; high level short
circuit strength)
Excellent dynamic response easily high cyclic loads.
Unique Design
Protect 8. UPS configurations:
Single systems
Parallel systems
Customized input/output voltages
Text translations to any language.
Parallel operation for capacity and performance:
Flexible Multi Master technology and Can-Bus communi-
cation up to 8 UPS to be connected in parallel for increased
power, redundancy or system upgrade
Parallel UPS can be operated with separated or central
battery.
Key Features
High and constant efficiency even at low output power:
Reduced operating costs
Reduced air conditioning requirements
Reduced battery Ah requirments.
Full digital control:
High reliability (no potentiometers)
High flexibility (software controlled parameters)
Fast dynamic response.
Oversized components ensure:
Higher reliability and MTBF
High overload capacity.
Redundant control for high reliability:
Separate microprocessors for rectifier, inverter, static switch
and communication
Separate, redundant power supplies for control cards.
Low maintenance cost
Ergonomic control unit with graphical display
Input isolation transformer
High short-circuit resistance
High EMC robustness compared to UPS Standard IEC 62040-2
by a factor of 2-to-3
Redundant and individually monitored fans
Floating 384V battery voltage for linking to existing DC bus
bars (160 - 500kVA)
Intelligent battery management, test and status diagnostics
Compatible with all battery types:
Vented lead acid
Valve regulated lead acid (VRLA)
Nickel cadmium.
Designed to operate with diesel generators
Additional system equipment:
Bypass transformer
Voltage stabilizer
Maintenance bypass switch
AC distribution panels
Battery cubicles
Explosion proof battery circuit breaker enclosures.
Full compatibility with all other AEG Power Solutions:
Industrial DC systems
Telecom systems.