User's Manual

Protect 8.33: Specification
Three Phase Output
MODEL P8.33-160 P8.33-220 P8.33-330 P8.33-400 P8.33-500
N
OMINAL RATING (AT COS 0.8 LAG)
IN KVA 160 220 330 400 500
RECTIFIER UNIT
Input nominal voltage 3
X 400 V (3 X 380 V, 3 X 415 V)
Input operating range (min/max) 340 V–460 V
Frequency 50/60 Hz ±10%
Input current in A at nominal load 259 357 535 649 811
Charging characteristic to IEC 478-10 IU
Nominal DC voltage
384 V
Rectifier type
- Standard 6 pulse 12 pulse 12 pulse 12 pulse 12 pulse
- Optional 12 pulse
INVERTER UNIT
DC input 384 V ± 20%
Nominal AC voltage 3x 400 V (3 x 380 V, 3 x 415 V)
Output voltage static response < ±1%
Output voltage dynamic response < ±2%
Recovery time
2 ms
Frequency
50/60 Hz
Frequency tolerance without mains ±0.1%
Frequency synchronisation range ±1% (±2%, ±3%)
Allowable load power factor 0.0 lag to 0.0 lead
Output phase current in A 231 318 477 578 723
Voltage wave form sinusoidal
Voltage distortion <3%
Crest factor max. 3
Overload response 1 min. 150%
Overload response 10 mn. 125%
Max short circuit current > 3 x I nom
STATIC BYPASS SWITCH
AC voltage 3
X 400 V (3 X 380 V, 3 X 415 V)
Frequency 50/60 Hz
Nominal power in kVA 160 220 330 400 500
GENERAL DATA
Efficiency (AC to AC) – typical up to 94% / >98% with ECO-Mode
Noise level depending on rating up to 74dB(A)
EMC compatibility EN 62040-2
Air cooling with redundant and monitored fans Yes
Operating temperature range min./max.
(without de-rating)
–5°C / +40°C
Storage temperature range min./max. –30°C / +75°C
Maximum altitude without de-rating 1000 m
Protection degree IEC 529/EN 60529
standard system
IP20, IP22 & IP43 (>IP43 engineered)
Equipment colour RAL 7035
WEIGHTS AND DIMENSIONS
Height standard UPS (mm) 1910 1915 1915 1915 1915
Height with max. options (mm) 2015 2210 2210 2210 2210
Width (mm) 1800 2100 3300 3300 3300
Depth (mm) 960 960 960 960 960
Weight (kg) 2410 2900 3970 4380 4980