User's Manual

31
Remarks
ParametersOperation display
Last
function
Main menu
= Main menu (appears after plugging in the LBA)
Submenu
Menu
next
submenu
Default
Value
User
Value
REMARK
Type setting dependent on the type
Some further menues are only accessible after input of a password.
Times
Approach 1. xx°e 60°el
60°el. in case of 1P, otherwise 90°el., default value for transformers
Softdown xx,xs 0.3
0 to (To-20ms), default value 400ms, ramp time up
Softdown xx,xs 0.3
0 to (To-20ms), default value 400ms, ramp time down
Cl.puls.dur xxxxxms 1.000 Display/Default of pulse period duration To
On-time xxxxms Display of on-time Ts
Sync.del. xxxms Display of on-time Ts
Min. pause 60ms Transformer dependent, default value
Puls.dur.max 50s Fixed parameter control range, default value,
password protection
Set pointm2 OFF/ON 9 OFF
On activating, a jump is made from the operation
display directly into this set point menu. The main
menu can be reached from here with the left key
.
9 Local/Remote
Set point menu 2 direct from the operation display
Local/Remote when parameter set point 2=ON
Motorp SW xx %, kW, A depending on set cascade control
Master SW xx
Total Pwr x %, total power; U1, I1 depending on set cascade
control
Total SW x Total set point value also in %, kW, V, A
Pa-lock OFF,ON OFF
With parameter lock ON, the lock, which is enabled
with OK, is reactivated after one minute of operation
display
Password
Password entry Enabling of password functions
----------------- Condition: Consultation/training
****** o.k. Valid until LBA is unplugged from the Power
Controller
-----------------
Code xxxxxxxxxx EEPROM version number
Operation display Current operation indication, exit using OK
U1
456,7V Display top
I1
1567,9A Display middle
P1
1234,8kW Display bottom
Status messages 11 Display of status information: select this line
and confirm using OK
11 State messages Examples for status indications
jjjjmmtt ddmmss
Limit
jjjjmmtt ddmmss
Limit
jjjjmmtt ddmmss
Undervoltage
Last function Return to the parameter last processed