3.1.9 LBA SUBMENUS WITH PASSWORD PROTECTION
REMARK
After password input, further parameters may be modifi ed. These are mainly adjusting parameters
required for achieving power control specifi cations. The modifi cation of these parameters requires
extended specialist knowledge (for instance by training) and is not required under normal circum-
stances.
3.2 CABINET INSTALLATION KIT (SEK)
Using the cabinet installation kit, the LBA may be installed in switching cabinet doors with a thick-
ness of up to 4 mm. It consists of an adaptor frame 96x72mm (cut-out dimensions 92x68mm) and
a cable. Using the cable, the LBA is connected to the RS 232 interface of Thyro-P.
The LBA locks in the adaptor frame and may only be removed with the cabinet door open. This
enables an instructed specialist to set parameters (for instance adjustment to changing tools) and
manual setting of set points (motor potentiometer) as well as for reading the actual value display
without opening the cabinet door (VBG4). In order to avoid the accidental input of data by touch-
ing the LBA, there is a self-activating parameterizing lock to enable (see Table 5).
If the LBA is connected to the Power Controller using a longer cable and does not operate, then
this may possibly be remedied by increasing the supply voltage (open the jumper R 155 in the
control device).
ATTENTION
In case of open jumper R 155, the LBA may not be connected to the Power Controller without
cable (hazard of destruction). The position of the jumper on the control device PCB can be found in
the component mounting diagram (Fig. 10, page 45).
3.3 THYRO-TOOL FAMILY
Thyro-Tool Familiy is an optional software for commissioning and visualization under Windows
95/98/NT 4.0/XP and higher. It includes all functions of Thyro-Tool P and it is connected to Thyro-P
via either one of the two standard interfaces (RS 232 respectively fi bre optic).
FIG. 8 CABINET
INSTALLATION KIT