11.6 Overload Protection
LED indications Warning
signal
LC displays Notes Operating
status /
Operating
problems
Normal
(Normal)
Battery
(On Battery)
Bypass
(Fault)
Fault
(Fault)
Overload in
normal operation
UPS warning
1 acoustic
signal
every 2 s
"Output
overload"
Reduce the load
Overload in
normal operation
> Switchover
Continuous
warning
signal
"Output
overload"Alarm
code: 46
Reduce the load
Overload in
battery operation
UPS warning
1 acoustic
signal
every 2 s
"Output
overload"
Reduce the load
Overload in
battery operation
> switch-off
Continuous
warning
signal
"Output overload"
Alarm code: 46
Reduce the load
Overload in
bypass
operation
1 acoustic
signal
every 2 s
"Output
overload"
Reduce the load
Note: = LED lights up
= LED flashes
If you cannot solve the problem that has occurred, stop the entire
procedure, switch off the UPS and disconnect the UPS from the
mains. Please contact our hotline in this case (see page 5).
Please have the serial number of the unit as well as the
purchase date at hand. The hotline will provide you with technical
support and can inform you about further procedures once you
have described the problem.