Operating instructions

Protect 5.31/xxx-480-220-120 10 kVA - 120 kVA
Page 10 of 56 8000020680 BAL, en
2 Technical Data
Please refer to the enclosed technical data sheet for optional and unit-specific setting
values.
Type kVA 10 20 30 40 60 80 100 120
Rated connection voltages
Voltage range in V
3 x 480 V ± 15 %
Frequency on rectifier input in Hz 45 - 66
Current consumption at
max. battery charge in A
19 36 54 72 110 147 181 216
Current consumption at trickle
charge in A
13 29 47 57 83 112 139 167
Rectifier output current I
AGR
in A
50 95 143 190 280 370 460 550
Intermediate circuit voltage in V
(rated voltage)
216 bei 108 Lead acid cells
voltage range 173 bis 260
Output voltage in V, neutral
conductor under full load
120 V
optional adjustable from 110 V - 127 V
Output current in A 83 167 250 333 500 667 833 1000
Output frequency in Hz
50 Hz ± 1 %
optional 60 Hz ± 1 %
THD factor in % at rated load
3 %
Overload capacity 1,5 x I
nom
for 1 minute
1,25 x I
nom
for 10 minutes
I
short circuit
(max) = 3 x I
nom
50 % Load Efficiency in %
Power loss in W
75 % Load Efficiency in %
Power loss in W
100 % Loadt Efficiency in %
Power loss in W
Outer dimensions in mm
without transport eyelets (IP20)
Height
Width
Depth
1810
600
850
1810
900
850
1810
1200
850
1810
1200
850
1810
1200
850
1810
2100
850
1810
2100
850
1810
2100
850
Weight in kg (approx.) 350 520 800 800 780 a/A* a/A* a/A*
Table 1 Technical data of the UPS
75