Operating instructions

Protect 5.31/xxx-480-220-120 10 kVA - 120 kVA
Page 47 of 56 8000020680 BAL, en
11 Interfaces
11.1 Remote Signalling
The remote signalling PCB consists of a remote signalling master
board A12 and an expansion board A13, the contacts of which are
connected to terminal block X12.
The remote signalling boards have the following inputs and outputs:
Inputs (via optocoupler):
INV remote shutdown
Outputs (via relay contacts):
Inverter operation
Mains operation
Rectifier fault (REC or REC circuit fault)
Battery undervoltage
Collective fault (REC, INV, SBS or battery fault)
SBS blocked
Fan fault
REC circuit fault
i
NOTE:
The maximum load for the relay contacts is 250 V / 8°A AC.
A
12-X3
Inverter
operation
Mains
operation
Rectifier
fault
Battery
undervoltage
A
ssign.
Meaning
Collective
fault
Inverter
remote
A
ssign.
Meaning
A
ssign. Meaning
X12
22
23
24
25
26
27
28
29
30
19
20
21
4
5
6
7
8
9
10
11
12
1
2
3
A
12-X4
X12
16
17
1
2
3
18
A
12-X5
X12
52
53
1
2
Figure 21 Terminal assignment of the remote signalling master board A12
i
NOTE:
The A13 and A14 expansion board can be programmed. See the
technical data sheet for terminal assignment.
The maximum input voltage for terminal X5 is 24 V AC/DC.
When a signal is received, the contacts on X3 close on the two
contact points with the lower numbers on the connection terminal.
The contacts on X4 close on the two connection terminals with the
higher numbers (fail-safe principle).
The control and message lines are routed to the bottom using the
cable duct in the centre of the unit.