Operating instructions

16
Charging time
(to 90 % of rated capacity) 6 h
Type Sealed, maintenance-free
PROTECT A. 1000 2 block batteries 12 V / 7 Ah
e.g. CSB, type GP1272F2 3-5 years acc. to EUROBAT
Yuasa, type NP7-12D Connection plug 6.3 mm
Panasonic, type LC-R127R2P (Faston 250)
PROTECT A. 1400 2 block batteries 12 V / 9 Ah
e.g. CSB, type HR1234WF2 3-5 years acc. to EUROBAT
Yuasa, type NPW7-12D Connection plug 6.3 mm
Panasonic, type UP-RW1245P1 (Faston 250)
Communication
Interfaces USB and RS232
Shutdown software on CD For all common operating
systems, e.g. Windows,
Linux, Mac, Unix, FreeBSD,
Novell, Sun
General data
Inherent noise (1 m distance) < 45 dB(A)
Operating temperature range 0 °C - 40 °C
Humidity 0 to 90 %
(without condensation)
Installation height Up to 1000 m
at nominal output
Housing colour Silver/black
Dimensions W x H x D [mm] 145 x 205 x 405
Weight [kg] 9.5 kg (PROTECT A. 1000)
10 kg (PROTECT A. 1400)
Cooling type Increased natural air cooling
Storage temperature range -15° C to +50° C
(UPS electronics)
UPS with integrated battery 0 °C to +40 °C
Conformity CE