Operation Manual

Protect PV.250 Operating Instructions
Page 28 of 51 80000027023 BAL, en
LED signals:
Green/red flashes: Configuration can be selected via the ter-
minal (up to 30 seconds after restarting)
Green on: Operating status; no external communica-
tion via X2 and X5
Green flashes: Data transmission on the serial interfaces
(X2 or X5)
Red on: Fault
Description of serial interfaces:
Port 1: Serial interface X2
The potential-free RS232 serial interface at connector X2 is
equipped with the AEG-specific CBSER protocol for parameter
setting and monitoring purposes. Special service tools can be used
to monitor and manage the system locally and (with the aid of the
COM server) remotely via a network. This is also the port used for
configuring the assembly's interfaces.
1
5
6
9
Fig. 12 Serial D-sub connector X2
Port 1 (X2): RS232 pin assignment
Pin number Signal Description
2 RxD PC receiving data from the MCC
3 TxD PC sending data to the MCC
5 GND Interface reference potential
Housing INV housing potential
Please use a 1:1 data cable for configuration purposes.
Port 2: Serial interface X5
The potential-free RS485 interface at connector X5 supports the
Modbus protocol for integration into higher-level monitoring sys-
tems.
1
5
6
9
Fig. 13 Serial D-sub connector X5