3.2.5.1 Treshold events
Some UPS models allow you to configure thresholds for releasing UPS specific threshold
events individually. CS121 also supports these features if the UPS includes this option. In this
case, you see at the main Event menu “Event configuration” at the bottom an additional link
“Configure threshold events”. Click here to add a new individual threshold event and you enter
the configuration page “Threshold Events”, within you get the possibilities to configure
individual events.
Figure 25: HTTP – Treshold event
3.2.5.2 Logfile entries
For a numerous of events logfile-entries are already pre-configured as default. To configure a
new logfile-entry, type in the field “Text” the desired message you wish to enter in the logfile
and choose the option on the right side, when/how often the message should appear in the
logfile.
Figure 26: HTTP - Job Editor: Logfile-entry
Example above: The text “Powerfail” will written into the logfile every 100 seconds for as long
as the event is present. Other actions on events such as Email, RCCMD-shutdown, UPS-
Dialer, TempMan etc. can be configured in the same way. Each event may have an unlimited
number of actions (executed now, delayed etc.).
Note: Do not forget to apply your changes before leaving the menu to send the
values to the CS121-adapter!
The CS121-logfile is located in the adapter root directory “../flash” The user can read the
Alarmlog-file using a FTP connection with the default IP address 10.10.10.10 or the configured
IP-address and the username/password combination “admin/cs121-snmp”. Alternatively the
logfiles can also be watched with the GENEREX monitor-tools UPSMON or JAVAMON resp.
via the Webbrowser. About the logfiles-contents please see also section 3.3 Reading the
Alarm-Logfile.