User manual

36
y=1 => switch on
y=0 => switch off
“20000” is the command to switch outputs. (for other commands please contact GENEREX
support)
Syntax examples:
|UPSCMD|20000|1,1 = Output 1 on
|UPSCMD|20000|1,0 = Output 1 off
|UPSCMD|20000|2,1 = Output 2 on
|UPSCMD|20000|8,0 = Output 8 off
Figure 32: HTTP - Job Editor: RCCMD-Command
Confirm a digital alarm : You can also use this syntax to e.g. confirm alarms for digital
inputs (e.g. Fire-alarm, door open, air-condition failed, etc.) which you see in the UNMS
software as “New Alarm”. E.g. if your UNMS software shows an active alarm and you want to
“acknowledge” this alarm by a switch witch you connected to a CS121 or SITEMANAGER,
than you can use the following syntax to program your device to send an “ACK” signal to the
receiver. After this your UNMS will show “Alarm acknowledged – recovery action in progress”.
Syntax : |UPSCMD|20001|x
where x is the Portnr. (1-8). („20001“ is the ACK command for digital signals)
Syntax example:
|UPSCMD|20001|2
This command confirms the Digital-Alarm 2 on a SITEMANAGER, SITEMONITOR,
SITESWITCH or CS121 AUX Inputs.
Confirm Analog-Alarm : The way it works with the ACK of analog alarms like Temperature
thresholds exceed on the UNMS.
Syntax : |UPSCMD|20002|x
where x is the Portnr. (1-8). („20002“ is the ACK command for for analog signals)
Syntax example:
|UPSCMD|20001|4
This command confirms the Analog-Alarm 4 on a SITEMANAGER, SITEMONITOR,
SITESWITCH or CS121 AUX Inputs.
3.2.5.4.6 RCCMD Trap
RCCMD Trap is the automatic messaging system of CS121, working with RCCMD clients. If
jobs have been configured in this category, the actions that are set here will be executed only
when an RCCMD client has established a connection to the UPSMON server of the CS121.