User manual

55
Figure 53: Exchange COM Ports 1 & 2 for SS4
6.1.1 SS4 Feature overview
4 configurable powers sockets with a breaking capacity of 230V/8A
Power socket status indicator via HTML, UPSMON, UNMS or SNMP
Control via the internal CS121 or via remote CS121 or RCCMD compatible devices
Remote control of the powers sockets via HTML Browser (Password protected)
LED-Status of the power sockets
Small metal casing with 1.5RU, designed for 19"-Rack Mountings (mounting frame included)
High breaking capacity (8A), input with IEC 16A.
Programmable power switching via the HTML and UPSMON Scheduler
Delay of alarm (e.g. UPS alarms) triggered power switching on COM1 of the CS121
6.1.2 SS4 Contents
SITESWITCH 4
16A IEC 230V power cable
2 mounting irons for 19“-Rack installation
manual for SS4
The manuals are being constantly updated and therefore the reader is encouraged to check
our website for a newer download version of the adapter manual. Check
http://www.generex.de for manual updates.
6.1.3 SS4 Installation
The power consuming devices are connected to the SS4 using IEC 250 VAC/6A plug cables.
The SS4 has 4 IEC 250VAC/6A chassis sockets that can be switched on and off separately.
Special notice is to be given to the 8A threshold breaking capacity; exceeding this limit will
cause the SS4 fuse to break leaving all connected devices without electricity.
Note: Due to errors that may cause the switched off power outlet to remain on
it is necessary to conduct the following: Before connecting any power
consuming devices with the SITESWITCH 4 or working on any power
consuming devices already connected to the SITESWTICH 4, make sure
that the SITESWITCH 4 is not connected to the power supply by pulling
its power cable out of the power socket.
Use the provided mounting irons to fix the SS4 into a 19“ rack. Place the SS4 so that the front
panel of the SS4 can be securely screwed onto the 19“ rack housing while insuring also that
the power cables can be connected from behind as well.
As soon as all of the power consuming devices are connected to the SS4, the IEC 16 power
supply cable can be connected. Upon establishing power to the SS4, the green „POWER„ LED
will light up, and the 4 „Power Socket Status LED“ one for each of the sockets should be unlit.
This means that none of the sockets are being provided with power thus cutting the connected
devices from the power supply.