User manual

70
ng interval
>= 3.5
charact
ers
number code count s of
the
word
interval
>= 3.5
charact
ers
RTU
HEX
high
byte
low
byte
low
byte
high
byte
[01] [04] [02] [12] [34] [B4] [47]
Æ The word at address contains the value 1234h = 4660 decimal.
D.5. UPS Parameter
Standard UPS – Address Description
Please note that this is just an example for a typical UPS, not every UPS has all these values,
some UPS may have more, some less. Please contact your UPS manufacturer to check which
variables are available and which requests are not supported.
Note: “Type U/S”: this defines whether the answer has an algebraic sign (math. +/-) or not. U
means “unsigned”. S means “signed”, this answer may be positive or negative.
Addr
ess
Type Funct
ion
Name Description Length
100 U 3 / 4 OUTP0WER0 Outpower Phase 1 1
101 U 3 / 4 OUTP0WER1 Outpower Phase 2 % 1
102 U 3 / 4 OUTP0WER2 Outpower Phase 3 % 1
103 U 3 / 4 BATTCAP Battery Capacity % 1
104 S 3 / 4 INVOLT0 Input Voltage Phase 1 V 1
105 S 3 / 4 INVOLT1 Input Voltage Phase 2 V 1
106 S 3 / 4 INVOLT2 Input Voltage Phase 3 V 1
107 S 3 / 4 TEMPDEG Temperature C° 1
108 S 3 / 4
A
UTONOMTIME
A
utonomy Time minutes 1
109 U 3 / 4 STATUS UPS Status (ASCII HEX)
Please note UPSMAN
statusbytes table below
1
10 S 3 / 4 BATTVOLT Battery Voltage V 1
111 U 3 / 4 INFREQ0 Input Frequency Hz Phase 1 1
112 U 3 / 4 INFREQ1 Input Frequency Hz Phase 2 1
113 U 3 / 4 INFREQ2 Input Frequency Hz Phase 3 1
114 U 3 / 4 CNT_PF Powerfail Counter 1
115 U 3 / 4
A
larm Battery Bad 1 = active; 0 = not active 1
116 U 3 / 4
A
larm: On Battery 1 = active; 0 = not active 1
117 U 3 / 4
A
larm: Battery Low 1 = active; 0 = not active 1
118 U 3 / 4
A
larm: Battery Depleted 1 = active; 0 = not active 1
119 U 3 / 4
A
larm: Over temperature 1 = active; 0 = not active 1
120 U 3 / 4
A
larm: Input Bad 1 = active; 0 = not active 1
121 U 3 / 4
A
larm: Output Bad 1 = active; 0 = not active 1
122 U 3 / 4
A
larm: Output Overload 1 = active; 0 = not active 1
123 U 3 / 4
A
larm: On Bypass 1 = active; 0 = not active 1
124 U 3 / 4
A
larm: Bypass Bad 1 = active; 0 = not active 1
125 U 3 / 4
A
larm: Output Off as
requested.
1 = active; 0 = not active 1
126 U 3 / 4
A
larm: UPS Off as requested. 1 = active; 0 = not active 1
127 U 3 / 4
A
larm: Charger Failed 1 = active; 0 = not active 1
128 U 3 / 4
A
larm: UPS Output Off 1 = active; 0 = not active 1
129 U 3 / 4
A
larm: UPS System Off 1 = active; 0 = not active 1
130 U 3 / 4
A
larm: Fan Failure 1 = active; 0 = not active 1
131 U 3 / 4
A
larm: fuse failure 1 = active; 0 = not active 1