Operating instructions

78
3.2.3 Current limitations
Potentiometer R203 enables the load current to be limited to a given value. Default
setting: nominal current as on type plate.
At reduced ambient temperature the controller can be operated with up to 110% of
its nominal current (effective value).
Analog output (setting guide)
5,5 V / 11.0mA = 200% - values 110% are limited to 110%
5 V / 10.0mA = 100%
2.5 V / 5.0mA = 50%
1.25V / 2.5mA = 25%
The permissible peak currents are derived from the fuse layout.
See type table and text: definitions and dimensions of Thyristor Power Controllers.
If the limit has been reached, the red LEDs blink in 1 sec. intervals.
3.2.4 Increased analog output
The analog output is adjusted to 0-20mA. 20mA corresponds to the actual r.m.s. cur-
rent which corresponds to the maximum permissible current of the Power Controller.
It is possible to adapt with potentiometer R204, e.g. if the scaling does not corres-
pond to the nominal data or the output is set to voltage reading. The increase can
be set to between 0 and 2.
Analog output (setting guide)
Factor
Remark
10 V / 20.0mA = 2 e.g. for 50A scale of a 100A device
5 V or 10.0mA = 1 see previous table
2.0V or 4.0mA = 0.4 e.g. for 100A scale of a 40A device
With voltage display the factor 1 corresponds to 110% of the type nominal voltage.
With output display (H RLP) with Thyro-A 1A the analog output signal corresponds to
U
type
* I
type
* 1.2.
With output display (H RLP) with Thyro-A 2A the analog output signal corresponds
to the total output of both power paths: Type power * 2 (type power according to
Table 9.1).
NOTE
Control characteristic and limitation P
max
work with U
type
* I
type
* 3
(enlarged by a factor of 1.2 to permit full drive at 10% overvoltage).