Operating instructions
Thyro-A 2A
load with joint neutral point without N
e.g.
parallel
load
resistances
Number
I
load nom.
/
I
type contr.
Resistance
increase
in case of fault
(L2)
Recommended
setting
for poti
R205
X2.9 [V]
X2.9
[0-20mA]
ca.
Revo-
lutions
1 100% 90.0% 9.0 18.0 14.0
1 80% 72.0% 7.2 14.4 11.5
1 60% (54%) 5.4 10.8 9.0
-----
-----
Tab. 2d Load monitoring
For Thyro-A 2A (load with joint neutral point without N conductor) the setting for
load monitoring can be made according to the table below:
82
Resistance
increase 20%
Load break
Resistance
increase 20%
Value deviations can be converted by percentage. The set monitoring value must
lie “in the middle” between the nominal load current value and the value after
outage.
NOTE
Settings above 90% and below 10% are not practical. If low load cur-
rents are required, check if a controller with a lower type current can
be used.
In the VAR operating mode monitoring with large trigger delay angles
C
140°el. is locked.