Operating instructions

98
ATTENTION
The induction of the load side transformer should not exceed 1.45T
in case of mains overvoltage when using grain-oriented, cold-rolled
plates = 1.2T nominal induction.
Betriebsarten
TAKT = full wave pulse = default (T
0
: 0.1 sec / 1.0 sec)
VAR = phase-angle control (only for types 1A)
QTM = fast half wave pulse (only for types 1A)
Set point inputs
The Power Controller Thyro-A has 2 set point inputs. The set point inputs are
indirectly connected to the mains (SELV, PELV).
Set point 1: External set point input signal ranges:
0(4) - 20mA R
i
= ca. 250k
0 - 5V R
i
= ca. 44k
0 - 10V R
i
= ca. 88k
Set point 2: Optional bus interface, connection from superset PC or automation
system.
Analogue output
Output: Signal level 0-10V, 0-20mA, 4-20mA
Maximum burden voltage 10V
10. Technical data
Type voltage 230V -15% +10% 99V with addit. 24V supply
400V -15% +10% 172V with addit. 24V supply
500V -15% +10% 200V with addit. 24V supply
Additional gate voltage input
The additional gate voltage supply can take place with a.c. or d.c.
24VAC +10% / -20%
24VDC +18V to +32V
Mains frequency all models 47Hz to 63Hz;
max. frequency change 5% per half wave
Load description ohmic load
ohmic load with R
hot
/ R
cold
ratio up to 6,
limit to î = 3 x I
nom
transformer load
Thyro-A 2A: symmetrical load