Operating instructions

42
Temperature behaviour DIN EN 60 146-1-1; K 2.2
Storage temperature D -25°C - +55°C
Transport temperature E -25°C - +70°C
Operating temperature better B -10°C - +35°C
with external cooling (280A)
-10°C - +45°C for self air cooling
-10°C - +55°C
with reduced type current -2%/°C
Load class 1 DIN EN 60 146-1-1 T.2
Humidity class B DIN EN 50 178 Tab. 7 (EN 60 721)
Overvoltage category III DIN EN 50 178 Tab. 3 (849V)
Degree of pollution 2 DIN EN 50 178 Tab. 2
Air pressure 900 mbar * 1000m above NN
Protection class I DIN EN 50178 Chap. 3
Safe isolation
Up to 500 V mains voltage DIN EN 50 178 Chap. 3
Air and creeping distances casing / mains potential 5.5 mm
casing / control potential 2.5 mm
mains voltage /contr. potent. 10 mm
mains volt. interactive 2.5 mm
Mechanical impact DIN EN 50 178 Chap. 6.2.1
Test voltage DIN EN 50 178 Tab. 18
Tests according to DIN EN 60 146-1-1 4.
EMV noise emission EN 61000-6-4
Noise suppr. control device Class A DIN EN 55011:3.91 CISPR 11
EMV noise resistance EN 61000-6-2
Compatibility level Class 3 EN 61000-2-4:7.95
ESD 8 kV (A) EN 61000-4-2:3.96
Electromagnetic fields 10 V/m EN 61000-4-3:3.95
Burst mains lines 2 kV (A) EN 61000-4-4:.95
control lines 2 kV (A)
Surge mains lines 2 kV unsym. EN 61000-4-5:.95
1 kV sym. EN 61000-4-5:.95
control lines 0.5 kV
Line-conducted EN 61000-4-6