User's Manual

OUTPUT MODE & TIMING FOR OUTPUT 1, 2 AND 3 (Locations 51, 52 &53)
The three relay outputs are programmable for Start/Stop or Timing modes. Apart from door access
control, alarm arm-disarm control, they are also universal timers for automatic operators in
industry with their 99,999 seconds (over 24 hours) programmable timer.
(1) LOCATIONS
-- Location for Output 1
-- Location for Output 2
-- Location for Output 3
(2) OUTPUT MODE & TIMING
Start /Stop Mode (Toggle)
The number 0 sets the output to Start / Stop mode. The output Starts when an User Code and/or
Card is entered/read; the output Stops when an User Code and/or Card is entered/read again.
-- Seconds Momentary --- (Default -- Momentary 5 Seconds)
The output can be set in Momentary Mode with the time of 1 second to 99,999 seconds. The
output will reset automatically when the time expires.
(3) VALIDATION
Press key once. Two-beep confirms the entry.
RESET OUTPUT TIMER WITH SUPER USER CODE
The Output Timer can be RESET manually at anytime with the Super User Code that operates
the desired output before the end of the time.
Example:
Reset Output 1 Timer -- ------------- Output 1 stops
Reset Output 2 Timer -- ------------- Output 2 stops
Reset Output 3 Timer -- ------------- Output 3 stops
SUPER USER CODE
SUPER USER CODE
SUPER USER CODE
High Traffic Passage:
A short buffer time may be necessary for opening a door outward after pressing the egress button
for those exits open to a high traffic passage. An egress button with short delay and warning beeps
helps the user to pay attention to the people passing by to prevent hitting them when the door is
pushed outward.
Emergency Exit:
Emergency Exit is not open to the public for daily use. It is for emergency case only. It is usually
closed and watched by guards. The egress button of this keypad can be programmed to offer exit
delay with warning beeps and even gives alarm output to trigger an alarm system when the door is
forced to open or the door is open after the exit delay expired. It is an useful tool to get attention of
the person on duty.
OUTPUT MODE & TIME VALIDATIONLOCATIONS

-

or
-

(3)(2)(1)


WARNING
Do not enable Egress Delay if instant door open for leaving is the main
concern in your area.
Make sure the Egress Delay does not affect the safety in your service
area before enabling the function in Location 90.
The default setting of the system is NO DELAY.