30 Clamp-on Ground Resistance Tester Model 6416
6.1.3 General Information
This information is displayed in both Standard and Advanced modes.
PRODUCT ZxI GREATER THAN 50V
- The blinking NOISE symbol is displayed.
- The impedance blinks.
- The hazardous voltage symbol blinks.
IMPEDANCE GREATER THAN 1500Ω
In this case:
- The impedance display indicates
(Over Range).
LEAKAGE CURRENT DISTURBANCE
If the current is greater than 5A, or if it is signi cantly
disturbed:
- The blinking NOISE symbol is displayed.
- The impedance blinks.
CURRENT GREATER THAN 10A
If the current is greater than 10A:
- The blinking NOISE symbol is displayed.
- The impedance is replaced by - - - -
CURRENT GREATER THAN 40A
If the current is greater than 40A:
- The current display indicates
(Over Range).