User Guide

Clamp-on Ground Resistance Tester Model 6416
31
6.2 Rotary Position (A)
In the A position, the clamp measures the electrical current, independently of any
ground/earth measurement.
If desired, con gure the current alarm threshold as desired (see §4.4, menu #6).
6.2.1 Making a Measurement
Turn the rotary switch to the A position, and wait several seconds while
the instrument performs internal calibration.
Clamp around the conductor to be measured. If the clamp is incorrectly
closed, the icon is displayed.
If necessary, use the HOLD button to freeze the measurement.
If necessary, use the MEM button to store the measurement.
Once the measurement has stabilized, the display will indicate the value of the
current  owing in the conductor.
NOTE: If the preset alarm threshold is
exceeded, the threshold set value and the
value of the current measured blink.

6.3 Rotary Position - (MR)
The MR position (Memory Recall) is used to display measurements previously
stored when the MEM button was pressed.
6.3.1 Displaying Stored Measurements
Set the function switch to the MR position.
The type of data that is displayed is dependent on whether Standard or
Advanced mode was selected during SET-UP (see § 4.4, menu #9).