PR1: 10/18//12 AERCO International Inc. 100 Oritani Dr. Blauvelt, NY 10913 Ph: 800-526-0288 Page 85 of 166
GF-120
OMM-0041 0E
Benchmark 1.5LN Low NOx Boiler
Installation, Operation and Maintenance Manual
Figure 7-4: RSI Manometer Installation Location
7.5 SAFETY DEVICE TESTING
Systematic and thorough tests of the operating and safety devices should be performed to
ensure that they are operating as designed. Certain code requirements, such as ASME CSD-1,
require that these tests be performed on a scheduled basis. Test schedules must conform to
local jurisdictions. The results of the tests should be recorded in a log book. See Chapter 6-
Safety Device Testing Procedures.
7.6 BURNER ASSEMBLY INSPECTION
The burner assembly (part no. 24012) is located at the top of the unit's heat exchanger. The
burner assembly may be hot. Therefore, allow the unit to cool sufficiently before removing the
burner assembly. It should be noted that the complete burner assembly also includes the blower
and air/fuel valve assemblies for the unit.
The following parts will be required for reassembly after burner inspection:
Part No.
Description
81063
Burner Gaskets (Qty=2)
81048
Flame Detector Gasket
81064
Blower Gasket
To inspect or replace the burner assembly: