Instruction Manual

Benchmark 750/1000 Boiler Installation, Operation & Maintenance Manual
CHAPTER 8 TROUBLESHOOTING GUIDE
Page 104 of 192 AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 OMM-0082_0J
05/21/2014 Ph.: 800-526-0288 GF-130
TABLE 8-1. BOILER TROUBLESHOOTING Continued
FAULT INDICATION
PROBABLE CAUSES
CORRECTIVE ACTION
AIRFLOW FAULT
DURING PURGE
1. Blower not running or running too
slow.
2. Defective Blocked Inlet switch.
3. Blockage in air filter or Blocked Inlet
switch.
4. Blocked blower inlet or inlet
ductwork.
5. No voltage to Blocked Inlet switch
from C-More Control Box.
6. PROBABLE CAUSES from 3 to 12
for AIRFLOW FAULT DURING
IGNITION apply for this fault.
1. Start the unit. If the blower does not run check the blower
solid state relay for input and output voltage. If the relay is
OK, check the blower.
2. Start the unit. If the blower runs, turn off unit and check the
Blocked Inlet switch for continuity. Replace the switch if
continuity does not exist.
3. Remove the air filter and Blocked Inlet switch and inspect for
signs of blockage. Clean or replace as necessary.
4. Inspect the inlet to the combustion blower including any
ductwork leading up to the combustion blower for signs of
blockage.
5. During the start sequence, verify that 24 VAC is present
between each side of the switch and ground. If 24 VAC is not
present, refer fault to qualified service personnel.
6. See CORRECTIVE ACTIONS from 3 to 12 for AIRFLOW
FAULT DURING IGNITION.
AIRFLOW FAULT
DURING RUN
1. Blower stopped running due to
thermal or current overload.
2. Blocked Blower inlet or inlet
ductwork.
3. Blockage in air filter or Blocked Inlet
switch.
4. Defective Blocked Inlet switch.
5. Combustion oscillations.
6. PROBABLE CAUSES from 3 to 16
for AIRFLOW FAULT DURING
IGNITION applies for this fault.
1. Check combustion blower for signs of excessive heat or high
current draw that may trip thermal or current overload
devices.
2. Inspect the inlet to the combustion blower, including any
ductwork leading up to the combustion blower, for signs of
blockage.
3. Remove the air filter and Blocked Inlet switch and inspect for
signs of blockage, clean or replace as necessary.
4. Verify that 24 VAC is present between each side of the switch
and ground. If 24 VAC is not present at both sides, replace
switch,
5. Run unit to full fire. If the unit rumbles or runs rough, perform
combustion calibration.
6. See CORRECTIVE ACTIONS from 3 to 12 for AIRFLOW
FAULT DURING IGNITION.