Instruction Manual

Benchmark 750/1000 Boiler Installation, Operation & Maintenance Manual
APPENDIX CSENSOR RESISTTANCE/VOLTAGE CHART
OMM-0082_0J AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 Page 149 of 192
GF-130 Ph.: 800-526-0288 05/21/2014
APPENDIX C: SENSOR RESISTANCE/VOLTAGE CHART
Temperature Sensor Resistance Voltage Chart (Balco)
TEMP (°F) RES (OHMS) VOLTS*
-40
-30
-20
-10
0
10
20
30
40
50
60
70
80
90
100
110
120
130
140
150
160
170
180
190
200
210
220
230
240
250
779.0
797.5
816.3
835.4
854.8
874.6
894.7
915.1
935.9
956.9
978.3
1000.0
1022.0
1044.4
1067.0
1090.0
1113.3
1137.0
1160.9
1185.2
1209.5
1234.7
1260.0
1285.6
1311.4
1337.7
1364.2
1391.0
1418.2
1445.7
1.93
1.96
1.99
2.02
2.05
2.07
2.10
2.12
2.15
2.17
2.20
2.23
2.25
2.27
2.30
2.32
2.34
2.36
2.39
2.41
2.43
2.45
2.47
2.50
2.52
2.54
2.56
2.58