Instruction Manual

Benchmark 750/1000 Boiler Installation, Operation & Maintenance Manual
APPENDIX MULTRA-LOW NOx CALIBRATION
OMM-0082_0J AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 Page 187 of 192
GF-130 Ph.: 800-526-0288 05/21/2014
Ultra-Low NOx Natural Gas Combustion Calibration Continued
NOTE
The remaining combustion calibration steps are performed using the
Combustion Cal Menu included in the C-More Control System. The combustion
calibration control functions will be used to adjust the oxygen level (%) at valve
positions of 80%, 60%, 45%, 30% and 18% as described in the following steps.
These steps assume that the inlet air temperature is within the range of 50°F to
100°F. If NOx readings exceed the target value of 9 ppm, increase the O
2
level
up to 1% higher than the listed calibration range. Record the increased O
2
value
on the Combustion Calibration sheet.
17. Lower the valve position to 80% using the ▼arrow key.
18. Press the MENU key on the front panel of the C-MORE and access the Setup menu. Enter
password 6817 and then press the ENTER key.
19. Press the MENU key on the front panel of the C-MORE until Combustion Cal Menu
appears on the display.
20. Press the ▲ arrow key until SET Valve Position appears on the display.
21. Press the CHANGE key. SET Valve Position will begin to flash.
22. Press the ▲ arrow key until SET Valve Position reads 80%. Press the ENTER key.
23. Next, press the
down (▼) arrow key until CAL Voltage 80% is displayed.
24. Press the CHANGE key and observe that CAL Voltage 80% is flashing.
25. The oxygen level at the 80% valve position should be as shown below. Also, ensure that the
nitrogen oxide (NOx) and carbon monoxide (CO) readings do not exceed the following
values:
Ultra-Low NOx Combustion Calibration Readings
Valve Position Oxygen (O
2
) %
Nitrogen Oxide
(NOx)
Carbon Monoxide
(CO)
80%
5% - 7%
<9 ppm
<100 ppm
26. If the oxygen level is not within the specified range, adjust the level using the and
arrow keys. This will adjust the output voltage to the blower motor as indicated on the
display. Pressing the arrow key increases the oxygen level and pressing the down
arrow key decreases the oxygen level.
27. Once the oxygen level is within the specified range at 80%, press the ENTER key to store
the selected blower output voltage for the 80% valve position. Record all readings on the
Combustion Calibration Sheets provided.
28. Repeat steps 20 through 27 for valve positions of 60%, 45%, 30% and 18%* (see *NOTE
below). The oxygen (O
2
), nitrogen oxide (NOx) and carbon monoxide (CO) should remain
within the same limits for all valve positions as shown in the following table.
*NOTE
Set the Valve Position at 18% but make adjustments to the Combustion
Calibration value designated as 16%.