Specifications

MODBUS COMMUNICATION MANUAL
2-8
Table 2-2. C-More Controller Standard Holding Register Address Mapping-Cont.
Modbus Data
Address (Hex)
Menu Item
Units and Range
Comments
0x0043 Sensor Log Interval Enum (0 to 8)
0 = Off
1 = 1 Min.
2 = 5 Min.
3 = 15 Min.
4 = 30 Min.
5 = 1 Hr.
6 = 6 Hrs
7 = 12 Hrs.
8 = 24 Hrs.
Default = 4 (30 min)
0x0044 Fault Log Pointer int 0 - 9
0x0045 Sensor Log Pointer int 0 - 1199
0x0046 Time Log Pointer int 0 - 10239
0x0047 Thru
0xFFFF
(Reserved) Available for future