Troubleshooting guide

APPENDIX F
TOP VIEWSIDE VIEW
INSTALLATION CLEARANCES
1) THIS APPLIANCE MAY BE INSTALLED ON COMBUSTIBLE FLOORING
24"
24"
24"
79"
18"
101"
2) MINIMUM CLEARANCES TO ADJACENT CONSTRUCTION ARE AS FOLLOWS:
LEFT AND RIGHT SIDES: 24''
FRONT: 24"
REAR: 43" (SEE NOTE)
CEILING HEIGHT: 101"
BENCHMARK 3 MIL. BTU LOW NOx
GAS FIRED BOILER
4" HIGH PAD
ZERO SIDE CLEARANCE INSTALLATION
FRONT
56"
NORTHVALE, NJ 07647
INTERNATIONAL, INC.
APPD.
DWN.BY
SCALE
DATE
MC
DATE
GS
061506
AERCO
SD-A-683 C
REV.
REAR
43"
78"
FOR ZERO SIDE CLEARANCE INSTALLATIONS
TWO UNIT SETS
4) THE ZERO SIDE CLEARANCE OPTION CAN ONLY BE EMPLOYED IN
3) THE INNER SIDE PANELS MUST BE REMOVED FROM BOTH UNITS
WHEN USING A REAR CLEARANCE OF LESS THAN 43", A 57" FRONT CLEARANCE
WILL BE NEEDED TO ALLOW THE REMOVAL OF EXHAUST CONNECTING MANIFOLD.
REAR CLEARANCE MAY BE REDUCED TO 24" DEPENDENT UPON PIPING AND VENTING
COMPONENT SELECTION, ARRANGEMENT, AND LOCAL CODE REQUIREMENTS. HOWEVER,
NOTE:
(SEE NOTE)
F-3
APPENDIX F
F-3