CHAPTER 7 – TROUBLESHOOTING GUIDE
OMM-0103_0A AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 Page 111 of 178
GF-147 Phone: 800-526-0288 PRI: 10/28/2014
7.2 ADDITIONAL FAULTS WITHOUT SPECIFIC FAULT MESSAGES
Refer to Table 7-2 to troubleshoot faults which may occur without a specific fault message being displayed.
TABLE 7-2: WATER HEATER TROUBLESHOOTING WITH NO FAULT MESSAGE DISPLAYED
OBSERVED INCIDENT PROBABLE CAUSES CORRECTIVE ACTION
Fluctuating Gas Pressure 1. Gas pressure going into unit is
fluctuating.
2. Damping Orifice not installed.
1. Stabilize gas pressure going into unit. If necessary,
troubleshoot Building Supply Regulator.
2. Check to ensure that the Damping Orifice is installed in the
SSOV Actuator shown in Figure 7-3. (For DBB Gas Trains,
the Damping Orifice is installed in the downstream SSOV
Actuator).
Air/Fuel Valve “hunting” at
the 80% Valve Position
1. IGST and Power Supply Boards in
Control Box are outdated.
1. Check to ensure that the IGST and Power Supply Boards
are Rev. E or higher.