User Manual

RECON Water Heaters Installation, Operation & Maintenance Manual
CHAPTER 2 – INSTALLATION
OMM-0103_0A AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 Page 27 of 178
GF-147 Phone: 800-526-0288 PRI: 10/28/2014
Condensate Trap Installation
1. Connect the condensate trap inlet to the exhaust manifold drain connection using the
appropriate piping components (nipples, reducers, elbows, etc.) for the heater installation
site. An example is shown in Figure 2-9.
2. At the condensate trap outlet, install a 3/4” NPT nipple.
3. Connect a length of 1” I.D. polypropylene hose to the trap outlet and secure with a hose
clamp.
4. Route the hose on the trap outlet to a nearby floor drain.
If a floor drain is not available, a condensate pump can be used to remove the condensate to
drain. The maximum condensate flow rate is 5 GPH for the RECON 500 and 8 GPH for the
RECON 1000. The condensate drain trap, associated fittings and drain line must be removable
for routine maintenance.
--WARNING! -
Use PVC, stainless steel, aluminum or polypropylene for
condensate drain piping (Figure 2-9). DO NOT use carbon or
copper components.
Figure 2-9: Sample Condensate Trap Installation
NOTE
Housekeeping pad should
not extend under the
condensate assembly
EXHAUST
MANIFOLD
3/4" NPT
NIPPLES
ADAPTER WITH
INTERNAL THREADS
TOP COVER
THUMB SCREWS
TO FLOOR DRAIN
UNION
CONDENSATE
TRAP
ADAPTER THUMB SCREW
1” I.D. HOSE
& CLAMP