CHAPTER 2 – INSTALLATION
OMM-0103_0A AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 Page 29 of 178
GF-147 Phone: 800-526-0288 PRI: 10/28/2014
2.10.2 Manual Gas Shutoff Valve
A manual shut-off valve must be installed in the gas supply line upstream of the Heater as
shown in Figure 2-10. The maximum allowable gas pressure to the unit is 14” W.C.
2.10.3 External Gas Supply Regulator
An external gas pressure regulator is required on the gas inlet piping under most conditions
(see sections 2.10.3.1 and 2.10.3.2, below). Regulators must conform to the following
specifications:
The external natural gas regulator must be capable of regulating 400,000 – 1,100,000
BTU/HR of natural gas while maintaining a gas pressure of 4.0” W.C. minimum to the
unit.
A lock-up style regulator MUST be used if gas supply pressure will exceed 14” W.C.
2.10.3.1
Massachusetts Installations Only
For Massachusetts installations, a mandatory external gas supply regulator must be
positioned as shown in Figure 2-10. The gas supply regulator must be properly vented to
outdoors. Consult the local gas utility for detailed requirements concerning venting of the
supply gas regulator.
2.10.3.2
All Installations (Except Massachusetts)
For all installations (other than Massachusetts) that exceed 7” W.C. gas pressure, a
mandatory external gas supply regulator must be positioned as shown in Figure 2-10. No
regulator is required for gas pressures below 7” W.C. of pressure. Consult the local gas utility
for detailed requirements concerning venting of the supply gas regulator.
Figure 2-10: Manual Gas Shut-Off Valve Location
MANUAL
SHUTOFF
VALVE
NATURAL GAS
SUPPLY
DIRT TRAP
GAS
PRESSURE
REGULATOR