CHAPTER 3 – OPERATION
Page 48 of 178 AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 OMM-0103_0A
PRI: 10/28/2014 Phone: 800-526-0288 GF-147
Menu Item Display
Available Choices or Limits
Default
Minimum Maximum
24 Temp Gov
Enable or Disable Enable
25 GOV Limit-5
0 100 30
26 GOV Limit-7
0 100 20
27 GOV Limit-10
0 100 15
28 GOV Limit-12
0 100 10
29 GOV Limit-15
0 100 5
30 PID Output
0% 100% Read Only Value
31 P Output
0% 100% Read Only Value
32 I Output
0% 100% Read Only Value
33 D Output
0% 100% Read Only Value
34 Reset Defaults
Yes No No
3.8 CALIBRATION MENU
The Calibration Menu is used by Factory Trained Service personnel to adjust or reset the
parameters listed below.
A full description of each item appears in Table A-5 of Appendix A – Recon Menu Item
Descriptions.
Table 3-6: Calibration Menu
Menu Item Display
Available Choices or Limits
Default
Minimum Maximum
1 Stepper Fbk
Cal 0%
Cal 100%
Verify 50%
Cal 0%
2 Purge Timer 5 sec. 60 sec Depends on unit type/size
3 Post Purge Timer 0 sec. 60 sec. 0 sec.
4 IGN Position 5% 60% Depends on unit type/size
5 FFWD Temp Disply Enabled or Disabled
6 Outlet Tmp Dsply Enabled or Disabled
7 Inlet Tmp Dsply Enabled or Disabled
8 Valv Pos Out Dsp Enabled or Disabled
9 Exhaust Tmp Dsp Enabled or Disabled
10 VP Up Rate 0.5 60.0 Depends on unit type/size
11 VP Down Rate 0.5 60.0 Depends on unit type/size
12 Purge Blwr Offst -1.0 8.0 Depends on unit type/size