CHAPTER 3 – OPERATION
Page 52 of 178 AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 OMM-0103_0A
PRI: 10/28/2014 Phone: 800-526-0288 GF-147
Start Sequence – Continued
4. Next, the blower proof switch on the Air/Fuel Valve (Figure 3-5) closes. The display will
show Purging and indicate the elapsed time of the purge cycle in seconds.
Figure 3-5: Blower Proof Switch
5. Upon completion of the purge cycle, the Control Box initiates an ignition cycle and the
following events occur:
(a)
The Air/Fuel Valve rotates to the low-fire ignition position and closes the ignition
switch. The dial on the Air/Fuel Valve (Figure 3-6) will read between 25 and 35 to
indicate that the valve is in the low-fire position.
(b)
The igniter relay is activated and provides ignition spark.
(c)
The gas Safety Shut-Off Valve (SSOV) is energized (opened) allowing gas to flow into
the Air/Fuel Valve.
BLOWER
PROOF
SWITCH
AIR/FUEL
VALVE
BLOCKED
INLET
SWITCH
AIR IN
TO BLOWER
GAS IN
STEPPER MOTOR
TRANSPARENT COVER