CHAPTER 4 – INITIAL START-UP
OMM-0103_0A AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 Page 61 of 178
GF-147 Phone: 800-526-0288 PRI: 10/28/2014
NATURAL GAS Combustion Calibration – Continued
Figure 4-4: Gas Pressure Adjustment Screw Location
13. Replace the brass cap on the SSOV gas pressure adjustment if it was previously removed.
14. With the valve position at 100%, insert the combustion analyzer probe into the flue probe
opening and allow enough time for the combustion analyzer reading to stabilize.
15. Compare the oxygen (O
2
)
level, carbon monoxide (CO), nitrogen oxide (NOx) and flame
strength readings with the range
shown in step 19, below. You may need to adjust O
2
% above
this range to meet ultra-low NOx requirements or to avoid combustion tone issues.
16. Press the MENU key on the front panel of the C-More until Combustion Cal Menu appears
on the display.
17. Press the arrow key until SET Valve Position reads 100%. Press the ENTER key.
18. Press the CHANGE key and observe that CAL Voltage 100% is flashing.
19. The oxygen level at the 100% valve position should be as shown below. Also, ensure that the
nitrogen oxide (NOx), carbon monoxide (CO) and flame strength readings match the following
values:
Combustion Calibration Readings
at 100% Valve Position
Valve
Position
Oxygen (O
2
)
%
Nitrogen Oxide
(NOx)
Carbon Monoxide
(CO)
Flame µA
100% 6.0% ± 0.25% <20 ppm <100 ppm > 6 µA
20. If the oxygen level is not within the specified range, adjust the level using the and arrow
keys. This will adjust the output voltage to the blower motor as indicated on the display.
Pressing the arrow key increases the oxygen level and pressing the down arrow key
decreases the oxygen level.
21. Once the oxygen level is within the specified range at 100%, press the ENTER key to store the
selected blower output voltage for the 100% valve position. Record all readings on the
Combustion Calibration Sheets provided.
22. Repeat steps 16 through 21 for the following valve positions (see NOTE below):
RECON 1000: 80%, 60%, 50%, 40%, 30%, 20%
RECON 500: 80%, 60%, 40%, 30%, 24%, 20%, 16%
BRASS HEX
HEAD CAP
(Remove to access gas
pressure adjustment screw)