CHAPTER 6 – MAINTENANCE
Page 94 of 178 AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 OMM-0103_0A
PRI: 10/28/2014 Phone: 800-526-0288 GF-147
Air Filter Replacement – Continued
5. Each replacement air filter is equipped with its own clamp. Therefore, simply install the
replacement air filter on inlet flange of the air fuel valve and tighten the clamp with a flat-tip
screwdriver or 5/16” nut driver.
6. Replace the side panels on the unit and return heater to service use.
Figure 6-11: Air Filter Mounting Location
6.11 LOW WATER CUTOFF (LWCO) CAPACITOR INTEGRITY TEST
The LWCO capacitor should be tested for electrical shorts every 12 months and replaced,
then tested, every 24 months. The LWCO capacitor integrity test consists of two parts, as
described in the next two sections. The first procedure explains how to test for electrical
shorting of the LWCO probe capacitor, while the second procedure instructs how to perform
the standard Low Water Cutoff test using the C-More controls.
On the Recon series, the LWCO probe is located on the heat exchanger body on the left side of
the unit. Refer to Figure 6-12 for an illustration of the LWCO probe assembly and its installation.
AIR/FUEL
VALVE
BLOWER
AIR FILTER
AIR FILTER
CLAMP