Operating Instructions and Installation Instructions

45
English
IFCW3LJ 1210 - 5375700_01
ELECTRICAL WIRING
Front panel
Power supply terminal block
Base
Electrical wiring
FCW213VN
FCW212VN
FCW313VN
FCW312VN
FCW413VN
FCW412VN
FCW21VLN
FCW31VLN
FCW41VLN
Motor
Terminal block
Connection
cable
Motor
Terminal block
Connection
cable
Motor
Terminal block
Connection
cable
Motor
Terminal block
Connection
cable
FCW213V
FCW212V
FCW21VL
FCW313V
FCW312V
FCW31VL
FCW413V
FCW412V
FCW41VL
Microprocess-
or controller
Terminal block
Connection
cable
Microprocess-
or controller
Terminal block
Connection
cable
FCW_2V
FCW_3V
FCW_VL
FCW_2VN
FCW_3VN
FCW_VLN
IG 2A
Cable cross section 1.5mm
2
WARNING: check that the power sup-
ply is disconnected before perform-
ing operations on the unit.
The unit must be connected directly
to an electrical outlet or to an inde-
pendent circuit.
Provide a 230V (±10%) power supply.
To protect the unit against short cir-
cuits, fit a circuit breaker of max.
2A 250V to the power line with a
minimum contact opening distance
of 3 mm.
The electrical power cable must be of
the H07 V-K or N07 V-K type with
450/750V insulation rating if inside
a tube or conduit. Use cables with
double H5vv-F type insulation for
exposed cable installation.
Follow the wiring diagram supplied
with the equipment and shown in this
document when making the connec-
tions.
Ensure that the installation is wired in
compliance with the laws and stand-
ards in force, and with the instruc-
tions in this manual.
All the parts and materials supplied on
site must comply with the local laws
and regulations.
WARNING
The unit must be correctly earthed; incorrect con-
nection could result in electric shocks or fires.