Operation Manual
15
INPUTS/OUTPUTS menu - Compressor magnet circuit breaker flow switch digital inputs
Visualisation on unit display Index Display/Parameter
A Inputs/Outputs: Indicates the state of the different entries/
exits.
B Master: indicates the type of data displayed; the displays can
be:
• Analogue inputs;
• Digital inputs;
• Digital outputs;
C 05: indicates the status of the flow switch positioned on the
evaporator, the status of this input can be one of the following:
• Closed = normal functioning;
• Open = minimum water flow rate threshold exceeded at the
evaporator (Flow switch alarm);
D
06: indicates the status of the compressor magnet circuit breaker
indicated, the status of this input can be one of the following:
• Closed = normal functioning;
• Open = the compressor load has exceeded the maximum
threshold (Compressor magnet circuit breaker alarm);
INPUTS/OUTPUTS menu - Compressor 2 magnet circuit breaker digital inputs and compressor phases
Visualisation on unit display Index Display/Parameter
A Inputs/Outputs: Indicates the state of the different entries/
exits.
B Master: indicates the type of data displayed; the displays can
be:
• Analogue inputs;
• Digital inputs;
• Digital outputs;
C
07: indicates the status of the compressor magnet circuit breaker
indicated, the status of this input can be one of the following:
• Closed = normal functioning;
• Open = the compressor load has exceeded the maximum
threshold (Compressor magnet circuit breaker alarm);
D 08: indicates the status of the phase control on the compres-
sors, the status of this input can be one of the following:
• Closed = normal functioning;
• Open = incorrect phases detected on the compressor indi-
cated (Serious alarm);
INPUTS/OUTPUTS menu - Evaporators pump magnet circuit breaker digital inputs
Visualisation on unit display Index Display/Parameter
A Inputs/Outputs: Indicates the state of the different entries/
exits.
B Master: indicates the type of data displayed; the displays can
be:
• Analogue inputs;
• Digital inputs;
• Digital outputs;
C/D 13-14: indicates the status of the evaporator pump magnet
circuit breaker indicated. The status of this input can be one of
the following:
• Closed = normal functioning;
• Open = the pump load has exceeded the maximum thresh-
old (Pump magnet circuit breaker alarm);
B
Input/Output
Master digital input
A
C
05= Evap.water flow:
Close
06= Ovrl.cmp.1 circ.1:
Close
D
B
Input/Output
Master digital input
A
C
07= Ovrl.cmp.2 circ.1
Close
08= Serious alarm:
Close
D
B
Input/Output
Master digital input
A
C
13= Ovrl.evap.pump 1:
Close
14= Ovrl.evap.pump 2:
---
D