Specification

Model: AP120 H-SL Series
6” Duct
Static Pressure (inches w.g.)
0.1
0.25
Air Volume (CFM)
120
111
Noise (sones)
0.7
n/a
Power Consumption (Watts)
33
32.3
Energy Efficiency (CFM/Watts)
3.6
3.4
Current (AMPS)
0.28
0.27
Grille Dimensions
13 3/8’ x 13 3/8”
Model
Qty
Project
Location
Architect
Engineer
Contractor
Submitted by
Date
Specifications
AP120 H-SL SERIES
Slim Fit Bathroom Fan with 8W 2700K LED Light
and Integrated Humidity Sensor
ETL Listed for installation over tub/shower enclosure with
GFCI circuit wiring.
Description: Slim fit bathroom fan with 8W 2700K 800 Lumens
LED light Engineered for continuous run Integrated user
adjustable humidity sensor Ceiling mount Suitable for new
construction or remodeling HVI certified ETL listed for use in
insulated ceilings (Type I.C.).
Motor/Blower: Permanently lubricated enclosed condenser motor
engineered for continuous energy efficient operation; power rating
120v/60Hz; motor equipped with thermal shut off.
Housing: Rugged 26 GA galvanized steel; 2 anti-vibration hangar
bar brackets adjustable to 24” span included; designed for ceilings
with a minimum of 6” clearance.
Duct: Detachable 4” and 6” duct connector with built-in back draft
dampener.
Grille: Contemporary design; low maintenance, wipe clean UV
inhibiting polymeric resin; attaches to housing with torsion springs.
Finishes: White (W); Satin Nickel (SN); Oil Rubbed Bronze (OR).
Light: 8W 2700K 800 Lumens LED light.
User-Adjustable Integrated Sensor: Humidity sensor adjustable
from 50-100% relative humidity (RH).
Installation: Must be installed by a licensed professional. Complete
installation instructions included.
Warranty: 6 Years
Architect’s Specifications: Ventilation fan will be ceiling mount
and no more than 0.7 sones at 120 CFM as certified by HVI at 0.1 Ps
(inches water gauge). Power consumption shall be no greater than 33
watts with an efficiency rating of no less than 3.6 CFM/watt. Light
shall be 8W 2700K LED light. Fan will begin operation when
humidity rises above user adjustable setpoint (50-100% RH). The
motor will be permanently lubricated, engineered for continuous
operation. Duct diameter will be 4” or 6” round. Fan shall be
ETL/cETL listed for tub/shower enclosure when used with GFCI
branch circuit wiring and shall be ETL/cETL listed for use in
insulated ceiling (Type I.C.).
Aero Pure, LLC 1006 Bankton Circle Ste B Hanahan, SC 29410 843.377.8642
www.aeropur efa n s . c om

Summary of content (1 pages)