Configuration Guide

EX5210R Exciter Installation & Configuration Guide
11
The Exciter has four connectors and two switches inside the back panel:
Figure 3: EX5210R Connector Wiring
(#1) Ethernet LAN Connection: RJ-45 connector. In a configuration with a
physical Ethernet cable connection to the LAN, the network cable is attached
here.
Permanent connection to a wired network is not mandatory. However, you
must have a wired connection to configure the Exciter. Some monitoring
functions are not available if the Exciter is not connected to the network. This
connection is also used for Power over Ethernet (PoE, 802.3af).
(#2) Power Jack: Accepts an input voltage of 24-48V DC. This is a standard 5.5
mm jack connector for direct power supply. The power Adaptor is not supplied
with the Exciter and can be purchased separately. When PoE is used, this
connector becomes redundant.
(#3) Chain IN: RJ-45 connector. This connector is used for receiving data from
Chained Exciters. The Chain IN port is also used to set the Exciter IP via the
Exciter Manager Application using a special 10-pin RJ45 to DB9 serial cable
(AeroScout SKU EXM-1000, or part of the Hardware Management kit).
(#4) Chain OUT and Control Connector: RJ-45 connector. This connector is
used for distributing power and data to Chained Exciters and to connect the
External LF Antenna device. The output voltage is 12 V DC (0.5A maximum).
(#5) Termination Switch: For defining the termination settings in a Chained
Exciters installation. The termination of the first and last Exciter in the chain
must be set to On (o-o) and the other Exciters set to Off: (-o-o-).
(#6) IP Reset: Restores the Exciter’s IP address to the company-set default
value. See Resetting the Exciter IP Address
for details.
1
2
3
4
5
6