User's Manual Part 1

User and Deployment Guide
29
Note
Connect to COM and NO if you want the switched circuit to be
on when the relay is on.
Connect to COM and NC if you want the switched circuit to be on
when the relay is off.
Connecting Programmable Outputs 3 and 4
The Controller has two programmable outputs. The outputs can be
programmed by the WanderGuard BLUE Manager to be activated when the
Controller enters a specific status/mode.
The outputs are automatically deactivated when the Controller is no longer in
that status/mode.
On the Controller's Terminal Block, the programmable outputs are designated
as follows:
x OUT3 on the Terminal Block – refers to programmable Output 3
x OUT4 on the Terminal Block – refers to programmable Output 4
Controller Modes and Relays
DAY MODE
x Relay 1 is activated upon TIF in order to lock the door
x Relay 1 returns to default upon TNIF
x After Bypass/Visitor code, Relay 1 gets deactivated
NIGHT MODE
x Relay 1 remains active during Night Mode
x Relay 2 gets activated when the door is opened. TIF is not necessary.
x Relay 2 returns to default when the Controller receives the reset code
x If Bypass/Visitor code is entered, Relay 2 remains in default for the
duration of the Bypass/Visitor Mode
x If Bypass/Visitor code is entered, Relay 1 is deactivated for the duration
of the Bypass/Visitor Mode