Cut Sheet
MC
10
AFC Cable Systems
800-757-6996 www.afcweb.com
Weights, Measurements and Packaging
Grounding Approx. Armor
Product Code Conductor Length (feet) Weight/1000 Minimum
Coil Reel Trade Size AWG Coil Reel Feet (lbs.) O.D. (inches)
1704B42T01 1704B60T01 12-2 Solid (brown) 12 250' 1000' 147 0.495
1704B42T02 1704B60T02 12-2 Solid (orange) 12 250' 1000' 147 0.495
1704B42T03 1704B60T03 12-2 Solid (yellow) 12 250' 1000' 147 0.495
1704B42T07 1704B60T07 12-2 Solid (purple) 12 250' 1000' 147 0.495
1705B42T01 1705B60T01 12-3 Solid (brown, orange) 12 250' 1000' 186 0.530
1705B42T02 1705B60T02 12-3 Solid (orange, yellow) 12 250' 1000' 186 0.530
1705B42T03 1705B60T03 12-3 Solid (brown, yellow) 12 250' 1000' 186 0.530
1705B42T07 1705B60T07 12-3 Solid (brown, purple) 12 250' 1000' 186 0.530
1706B42T01 1706B60T01 12-4 Solid (brown, orange, yellow) 12 250' 1000' 223 0.565
1706B42T07 1706B60T07 12-4 Solid (brown, yellow, purple) 12 250' 1000' 223 0.565
1758B42T01 1758B60T01 12-2 Stranded (brown) 12 250' 1000' 152 0.495
1758B42T02 1758B60T02 12-2 Stranded (orange) 12 250' 1000' 152 0.495
1758B42T03 1758B60T03 12-2 Stranded (yellow) 12 250' 1000' 152 0.495
1759B42T01 1759B60T01 12-3 Stranded (brown, orange) 12 250' 1000' 191 0.530
1760B42T01 1760B60T01 12-4 Stranded (brown, orange, yellow) 12 250' 1000' 225 0.565
1707B42T01 1707B60T01 10-2 Solid (brown) 10 250' 1000' 222 0.560
1707B42T02 1707B60T02 10-2 Solid (orange) 10 250' 1000' 222 0.560
1707B42T03 1707B60T03 10-2 Solid (yellow) 10 250' 1000' 222 0.560
1707B42T07 1707B60T07 10-2 Solid (purple) 10 250' 1000' 222 0.560
1708B42T01 1708B60T01 10-3 Solid (brown, orange) 10 250' 1000' 268 0.600
1708B42T02 1708B60T02 10-3 Solid (orange, yellow) 10 250' 1000' 268 0.600
1708B42T03 1708B60T03 10-3 Solid (brown, yellow) 10 250' 1000' 268 0.600
1708B42T07 1708B60T07 10-3 Solid (brown, purple) 10 250' 1000' 268 0.600
1709B42T01 1709B60T01 10-4 Solid (brown, orange, yellow) 10 250' 1000 313 0.645
1709B42T07 1709B60T07 10-4 Solid (brown, yellow, purple) 10 250' 1000' 313 0.645
1761B42T01 1761B60T01 10-2 Stranded (brown) 10 250' 1000' 227 0.560
1762B42T01 1762B60T01 10-3 Stranded (brown, orange) 10 250' 1000' 269 0.600
1763B42T01 1763B60T01 10-4 Stranded (brown, orange, yellow) 10 250' 1000' 319 0.645
MC TUFF
®
Lightweight Steel Metal Clad Cable
(480Y/277 Volt colors) Technical Specifications
NOTE: All dimensions and weights are subject to normal manufacturing tolerances. Other conductor colors available by special order. WARNING: DO NOT RE-IDENTIFY CONDUCTOR COLORS.
Additional brown stripe denotes
2 conductor cable (brown conductor)
Additional orange stripe denotes
2 conductor cable (orange conductor)
Additional yellow stripe denotes
2 conductor cable (yellow conductor)
Additional purple stripe denotes
2 conductor cable (purple conductor)
Additional brown and orange stripes
denote 3 conductor cable
Additional orange and yellow stripes
denote 3 conductor cable
Additional brown and yellow stripes
denote 3 conductor cable
Additional brown and purple stripes
denote 3 conductor cable
Additional brown, orange and
yellow stripes denote 4 conductor cable
Additional brown, yellow and purple
stripes denote 4 conductor cable
Galvanized Steel Armor
(Color-Coded Blue)
Cable Tape
Copper
Conductors
Nylon Thermoplastic
THHN Insulation
Copper
Ground
Gray
Insulated
Neutral
Specification Description
Specification MC TUFF
Armor Galvanized Interlocking Steel Strip
(blue striped)
Conductors Solid or Stranded Copper
Conductor THHN (XHHW available by special
Insulation order subject to lead time and
minimum quantities)
Assembly Covering Polypropylene tape
Maximum
Temperature 90°C (dry)
Rating
Grounding One grounding means – Insulated
Green Grounding Conductor
(additional insulated
conductors optional)
Neutral Gray
Conductor
Maximum 600V
Voltage Rating
References & Ratings
•U.L. 83, 1479, 1569, 1581,
File Reference E80042
•NEC 230.43, 300.22(C), 392, 396,
330, 518, 520, 530, 645
•Cable Tray installations per NEC
•Federal Specification A-A-59544
(formerly J-C-30B)
•Meets all applicable OSHA and HUD requirements
• May be surfaced mounted and embedded in plaster
•Environmental Air-Handling Space installation
•U.L. Classified 1, 2 and 3-hour through-penetration Fire Wall
AFC’s Color-Coded Armored Cable System
SET SCREW CONNECTORS MAY BE USED WITH STEEL CABLES, SEE CONNECTOR CROSS-REFERENCE GUIDE PAGE 30 FOR DETAILS.