Installation Manual

PRESSURE TESTING
The pressure test point is situated just below hotplate level on the rear right hand side of the range. (See Fig. 12).
The maximum gas inlet pressure to the appliance must not exceed 10” w.g. for Natural gas and 14” for L.P. gas. The min-
imum gas inlet pressure at the appliance must not be less than 5” w.g. Natural gas and 11” w.g. for L.P. gas to enable the
correct manifold pressure to be obtained.
NOTE: The regulator is preset for either Natural gas or L.P. gas.
For Natural gas manifold pressure is 4” w.g.
For L.P.G. (propane only) manifold pressure is 10” w.g.
Re-fit test point blanking screw and check for gas tightness.
Fig.14 DESN 517235
POSITION OF GAS CONNECTOR ON WALL (located in shaded area)
IMPORTANT: THE GAS SUPPLY CONNECTION AT THE WALL MUST NOT PROJECT OUT FROM THE WALL
BY MORE THAN 1
3
/4” (45mm), SO THAT IT DOES NOT FOUL WITH THE BACK OF THE RANGE.
17
LOCATION AREA
FLEXILINE
CONNECTOR