Service manual

8-16 11713A Operating and Service Manual
Servicing the Attenuator/Switch Driver
Troubleshooting the A3 Latch Assembly
Troubleshooting the A3 Latch Assembly
The A3 latch assembly contains 10 J-K flip-flops and a power-up circuit.
To Troubleshoot the A3 Latch Assembly
1. If any of the following conditions cannot be met, replace the A3 latch
assembly.
a. Turn the power off and then turn it on again. All attenuator lights
and the local light should be on.
b. Press each attenuator switch. Only the corresponding light
should turn off. No other light should flicker or change status.
c. Send a remote command to turn the attenuators off and then on.
All attenuators should come on.
d. Send a remote command to individually control each light
OFF/ON. Only the corresponding light should turn off. No other
fight should flicker or change status.
2. If these tests are inconclusive, test the Al interconnect, A7 switch,
AS GPIB, and A4 remote local logic board assemblies in this
sequence before replacing the A3 latch assembly.
Assembly Overview
When the driver is in the local mode, the J and K inputs to all ten
flip-flops are in the logic high state. The flip-flops then operate as
"toggle" flip-flops and respond to the front panel pushbuttons. The
pushbuttons function as clock pulses for the flip-flops.
In the remote state, the A4 assembly A or B flip-flop controls the J, K
inputs. In the A state, the J inputs are in the logic low state and the K
inputs are logic high.
The decoder on the A4 assembly generates the clock pulses for each
flip-flop. In the A state, flip-flops 1 through 10 are set so the Q = 1 and
NQ = 0. In the B state J inputs = 1 and K inputs = 0. Clock impulses
from the decoder set flip-flops 1 through 10 on the negative edge as
commanded by the bus.
The power-up circuit sets the state of all flip-flops so that the
instrument powers up in the local state and with all switches set to the
A (LEDs on) condition. Any attenuators connected to the driver are set
to maximum attenuation on power up.