Product specifications

98
Multiple-Input: 150 W to 600 W (Continued)
Table A-1 Specifications
Table A-1 lists the specifications
for the different load models.
Specifications indicate wa rranted
performance in the 2C ±5°C
region of t he operating tempera -
ture range. S pecifications apply
to normal and t ransient modes
unless otherwise noted.
Input characteristic
Notes
1
Maximum continuous power available
is derated linearly from 100% of
maximum at 40°C, to 75% of maximum
at 55°C.
2
Specification is ± (% of reading + fixed
offset). Measurement is 1000 samples.
Specification may degrade when the
unit is subject to an RF field of
3 V/meter, the unit is subject to
line spikes of 500 V, or an 8 kV
electrostatic discharge.
3
DC current accuracy specifications
apply 30 seconds after input current
is applied.
N3302A N3303A N3304A N3305A N3306A N3307A
Input ratings
Current 0 - 30 A 0 - 10 A 0 - 60 A 0 - 60 A 0 - 120 A 0 - 30 A
Voltage 0 - 60 V 0 - 240 V 0 - 60 V 0 - 150 V 0 - 60 V 0 - 150 V
Maximum power @ 40°C
1
150 W 250 W 300 W 500 W 600 W 250 W
Specified current @
low voltage operation
2.0 V 30 A 10 A 60 A 60 A 120 A 30 A
1.5 V 22.5 A 7.5 A 45 A 45 A 90 A 22.5 A
1.0 V 15 A 5 A 30 A 30 A 60 A 15 A
0.5 V 7.5 A 2.5 A 15 A 15 A 30 A 7.5 A
0 V 0 A 0 A 0 A 0 A 0 A 0 A
Typical minimum operating Table A-1 states that maximum current is available down to 2 volts. Typically,
voltage @ full scale current however under normal operating conditions, the load can sink the maximum
current down to the following voltages:
1.2 V 1.2 V 1.2 V 1.4 V 1.4 V 1.4 V
Constant current mode
2
Low range/high range 3 A/30 A 1 A/10 A 6 A/60 A 6 A/60 A 12 A/120 A 3 A/30 A
Regulation 10 mA 8 mA 10 mA 10 mA 10 mA 10 mA
Low range accuracy 0.1% + 5 mA 4 mA 7.5 mA 7.5 mA 15 mA 7.5 mA
High range accuracy 0.1% + 10 mA 7.5 mA 15 mA 15 mA 37.5 mA 15 mA
Constant voltage mode
2
Low range/high range 6 V/60 V 24 V/240 V 6 V/60 V 15 V/150 V 6 V/60 V 15 V/150 V
Regulation 5 mV 10 mV 10 mV 10 mV 20 mV 10 mV
Low range accuracy 0.1% + 3 mV 10 mV 3 mV 10 mV 3 mV 10 mV
High range accuracy 0.1% + 8 mV 40 mV 8 mV 20 mV 8 mV 20 mV
Constant resistance mode
2
Range 1
(I >10% of current rating) 0.067-4 Ω 0.2-48 Ω 0.033-2 Ω 0.033-5 Ω 0.017-1 Ω 0.067-10 Ω
Range 2
(I >1% of current rating) 3.6-40 Ω 44-480 Ω 1.8-20 Ω 4.5-50 Ω 0.9-10 Ω 9-100 Ω
Range 3
(I >0.1% of current rating)
36-400 Ω 440-4800 Ω 18-200 Ω 45-500 Ω 9-100 Ω 90-1000 Ω
Range 4 (I >0.01% of current rating)
360-2000 Ω 4400-12000 Ω 180-2000 Ω 450-2500 Ω 90-1000 Ω 900-2500 Ω
Transient generator
Frequency range
0.25 Hz- 0.25 Hz- 0.25 Hz- 0.25 Hz-
0.25 Hz 0.25 Hz-
10 kHz 10 kHz 10 kHz 10 kHz
10 kHz 10 kHz
Pulse width
50 µs ±1% to 50 µs ±1% to 50 µs ±1% to 50 µs ±1% to 50 µs ±1% to 50 µs ±1% to
4 seconds ±1% 4 seconds ±1% 4 seconds ±1% 4 seconds ±1% 4 seconds ±1% 4 seconds ±1%
Current measurement
2
Low range/high range 3 A/30 A 1 A/10 A 6 A/60 A 6 A/60 A 12 A/120 A 3 A/30 A
Low range accuracy
3
0.05% + 3 mA 2.5 mA 5 mA 5 mA 10 mA 3 mA
High range accuracy
3
0.05% + 6 mA 5 mA 10 mA 10 mA 20 mA 6 mA
Voltage measurement
2
Low range/high range 6 V/60 V 24 V/240 V 6 V/60 V 15 V/150 V 6 V/60 V 15 V/150 V
Low range accuracy 0.05% + 3 mV 10 mV 3 mV 8 mV 3 mV 8 mV
High range accuracy 0.05% + 8 mV 20 mV 8 mV 16 mV 8 mV 16 mV
Power measurement
2
Accuracy 0.1% + 0.5 W 1.2 W 0.5 W 1.5 W 1.2 W 0.5 W
More detailed specifications at
www.agilent.com/find/N3300
DC Electronic Loads maximize throughput with real-life loading conditions
Operating contour
Voltage
full
scale
full
scale
Current
full
scale
Current
0
Max. Power Contour
Derated current detail
Voltage
full
scale
0
1
2
3
all specifiations apply
slew rate limitations apply
(see Table A-2)