Product specifications
Section 5 Maintenance PROFIBUS DP – CI851
3BSE036351-510 A 209
PROFIBUS DP – CI851
Table 31. PROFIBUS DP CI851 – Fault-Finding 
Fault Possible Cause and Corrective Action
Neither R(un) nor F(ault) LEDs 
are ON
The CI851 board is in the process of being re-
started or configured. Allow time for this to finalize.
If the condition persists, and all other units on the 
CEX-Bus have non-illuminated LEDs:
• Check that a valid HW configuration including 
the CI851 is downloaded to the controller.
• Check the CEX-Bus fuse inside the PM8xx 
processor unit.
• Initiate a reset signal (INIT) from the PM8xx 
processor unit.
• Replace the CI851 unit.
F(ault) LED is ON Check all cables and connectors for damage, 
loose or incorrect terminations.
• Repair as necessary.
R(un) LED is flashing Check that the relevant units are sending data.
Check if the CI851 board is in the process of 
being restarted or configured. If so, allow time for 
this finalize.
If the condition persists:
• Halt the application program and initiate a 
restart.
• Replace the CI851 board.