Hot swap of the BC810 located next to a primary or single controller CPU, 
otherwise called “direct BC810”, might jeopardize the whole controller and 
should not be performed unless every module on the CEX-Bus are in a non-
operating state. Note: In an AC 800M HI controller this is unconditionally and 
intentionally leading to a shutdown of the controller.
Hot swap of the BC810 not located next to a primary or single controller CPU, 
otherwise called “indirect BC810”, will shut down any non-redundant interface 
located on that CEX-Bus segment and should not be performed unless such 
interfaces already are in a non-operating state or their function is dispensable for 
the controller.