User`s manual
58 Agilent E1330B Digital I/O Module Command Reference
Chapter 5
Command
Separator
A colon (:) always separates one command from the next lower level command. This 
is illustrated as follows:
MEASure:DIGital:DATAn:VALue?
Colons separate the root command from the second level (MEASure:DIGital) and the 
second from third level (
DIGital:DATAn), and so forth.
Abbreviated
Commands
The command syntax shows most commands as a mixture of upper and lower case 
letters. The upper case letters indicate the abbreviated spelling for the command. For 
shorter program lines, send the abbreviated form. For better program readability, you 
may send the entire command. The instrument will accept either the abbreviated 
form or the entire command.
For example, if the command syntax shows 
MEASure, then MEAS and MEASURE 
are both acceptable forms. Other forms of 
MEASure, such as MEASU or MEASUR 
will generate an error. You may use upper or lower case letters. Therefore, 
MEASURE, measure, and MeAsUrE are all acceptable.
Command keywords can be entered in their full form, as shown above, or can be 
entered in their short form. In this manual, the entry required in short form 
commands is always capitalized. The short form is generally used for examples in 
this manual.
Implied
Commands
Implied commands are those which appear in square brackets ([]) in the command 
syntax. (Note that the brackets are not part of the command and are not sent to the 
instrument.)  Suppose you send a second level command but do not send the 
preceding implied command. In this case, the instrument assumes you intend to use 
the implied command and it responds as if you had sent it. Examine this excerpt from 
the 
[SOURce:] subsystem shown below:
[SOURce:]
DIGital
:DATA
n
[:VALue] <parameter>
:BIT
m <parameter>
Both the root command [SOURce:], and forth level command [:VALue], are implied 
commands. To set the instrument to output a logical 1 to bit 0 of port 3, you may send 
either:
SOURce:DIGital:DATA3:BIT0 1 or DIGital:DATA3:BIT0 1
Note You must include a space between the keywords and any parameters.