AIMS Power www.aimscorp.net Global LF Series Pure Sine Wave Inverter/ Chargers 5-12KW User’s Manual Version 4.
AIMS Power www.aimscorp.net Table of Contents 1. Important Safety Information ........................................................................................................................ 3 1-1. General Safety Precautions ......................................................................................................................... 3 1-2. Precautions When Working with Batteries ................................................................................................ 3 2.
AIMS Power www.aimscorp.net 1. Important Safety Information WARNING! Before using the Inverter, you need to read and save the safety instructions. 1-1. General Safety Precautions 1-1-1.Do not expose the Inverter to rain, snow, spray, bilge or dust. To reduce risk of hazard, do not cover or obstruct the ventilation openings. Do not install the Inverter in a zero-clearance compartment. Overheating may result. Allow at least 30CM of clearance around the inverter for air flow.
AIMS Power www.aimscorp.net 2. Introduction 2-1. General Information Global LF Series Pure Sine Wave Inverter is a combination of an inverter, battery charger and AC auto-transfer switch into one complete system with a peak conversion efficiency of 88%. It is packed with unique features and it is one of the most advanced inverter/chargers in the market today.
AIMS Power www.aimscorp.net 2.3 Mechanical Drawing The PICOGLF 5-12KW inverters may come in two differente enclosures.
AIMS Power www.aimscorp.
AIMS Power www.aimscorp.
AIMS Power www.aimscorp.
AIMS Power www.aimscorp.
AIMS Power www.aimscorp.net 2-4.
AIMS Power www.aimscorp.net Global LF Series is equipped with an active PFC (Power Factor Corrected) multistage battery charger. The PFC feature is used to control the amount of power used to charge the batteries in order to obtain a power factor as close as possible to 1.
AIMS Power Battery type selector Switch setting 0 1 2 3 4 5 6 7 8 9 www.aimscorp.net Description Charger Off Gel USA AGM 1 AGM 2 Sealed lead acid Gel EURO Open lead acid Calcium De-sulphation Not used Boost / Vdc Float / Vdc 14.0 14.1 14.6 14.4 14.4 14.8 15.1 15.5 (4 Hours then Off) 13.7 13.4 13.7 13.6 13.8 13.3 13.
AIMS Power www.aimscorp.net For 12VDC models: after the battery voltage goes below 10V and the power switch is kept in the "ON" position and the inverter stays connected to the battery and the battery voltage doesn’t drop below 2V, the inverter will be able to charge the battery once qualified AC inputs are present. Before the battery voltage goes below 9VDC, the charging can be activated when the switch is turned to “Off”, then to “ON”.
AIMS Power www.aimscorp.net All our Global LF line of inverters have a 50/60 hz selector switch. When the inverter is turned off and shore power is not present, the frequency of the inverter may be selected to be 50 or 60 hz. 2.5.5 Power Saver There are 2 different working statuses for our Global LF inverter: “Power On” and “Power Off”. When the power switch is in “Unit Off” position, the inverter is powered off.
AIMS Power www.aimscorp.net PICOGLF60W24V120V 87 35 80.7 30.3 87 35 100 30 PICOGLF10KW48V230VS 150 35 PICOGLF12KW48V230VS 200 40 PICOGLF60W48V230V PICOGLF60W48V230VS PICOGLF60W48V120V PICOGLF80W48V230VS When in the search sense mode, the green power LED will blink and the inverter will make a ticking sound. At full output voltage, the green power LED will light steadily and the inverter will make a steady humming sound.
AIMS Power www.aimscorp.net Apart from the switch panel on the front (or top) of the inverter, an extra switch panel connected to the RJ11 port at the DC side of the inverter thru a standard telephone cable can also control the operation of the inverter (sold separately Part # PICGLFREMOTE). If an extra switch panel is connected to the inverter via “remote control port”, together with the panel on the inverter case, the two panels will be connected and operated in parallel.
AIMS Power SHORE POWER ON INVERTER ON FAST CHARGE FLOAT CHARGE OVER TEMP TRIP OVER LOAD TRIP POWER SAVER ON www.aimscorp.
AIMS Power www.aimscorp.net 2.5.9 Audible Alarm Inverter green LED lit, and the buzzer beeps 0.5s every 5s. Inverter green LED lit, and the buzzer beeps 0.5s every 1s and Fault after 60s. (1)110%150%(±10%), Beeps 0.5s every 1s and Fault after 20s; Heat sink temp. ≥105ºC(221℉), Over temp red LED Lighting, beeps 0.
AIMS Power SW4 SW5 www.aimscorp.net ON/OFF Frequency Switch Battery/AC Priority 50Hz AC Priority 60Hz Battery Priority Low Battery Trip Point(SW1): Deep discharge of the lead acid battery leads to high losses in capacity and early aging. In different applications a different low voltage disconnection level is preferred. For example, for solar applications, user may intend to have less DOD to prolong the battery life cycle.
AIMS Power www.aimscorp.net The output frequency of the inverter can be set at either 50Hz or 60Hz by SW4. AC/Battery Priority(SW5): Our inverter is designed with AC priority by default. This means, when AC input is present, the battery will be charged first, and the inverter will transfer the input AC to power the load. Only when the AC input is stable for a continuous period of 15 days will the inverter start a battery inverting cycle to protect the battery.
AIMS Power www.aimscorp.net Battery voltage recovery start After low battery voltage shut off (10V for 12V model or 20V for 24V model or 40V for 48V model), the inverter is able to restore operation after the battery voltage recovers to 13V/26V/52V (with power switch still in the “On” position). This function helps to save the users extra labor to reactivate the inverter when the low battery voltage returns to an acceptable range in renewable energy systems.
AIMS Power www.aimscorp.net 5KW 5KW 6KW 6KW 8KW 10KW 12KW 24Vdc 48Vdc 24Vdc 48Vdc 48Vdc 48Vdc 48Vdc AWG 4/0 AWG 1/0 AWG 4/0 AWG 1/0 AWG 3/0 AWG 3/0 AWG 3/0 Performance of any product can be improved by thicker cable and shorter runs, so if in doubt, round up and keep the length as short as possible. For more wiring configurations for your specific system, please contact AIMS Power for more information. CAUTION The torque rating range for DC terminal is 12.5NM-20.
AIMS Power www.aimscorp.net Wiring Option 2 230V split phase Input: Hot line+ Hot line +Ground Output: Hot line+ Hot line +Neutral Wiring Option 3 230V split phase Input: Hot line+ Hot line +Ground Output: Hot line +Neutral Remark: In such case, each output hotline can only carry a max of half the rated capacity. Caution: Wiring Option 2 and 3 are only allowed for split phase models (last letter of part # “S”). Pls wire all the other models according to Wiring Option 1.
AIMS Power www.aimscorp.net 3.4 Grounding Connect an AWG 8 gauge or greater copper wire between the grounding terminal on the inverter and the earth grounding system or the vehicle chassis. 3.
AIMS Power www.aimscorp.
AIMS Power www.aimscorp.net 4 Troubleshooting Guide Troubleshooting contains information about how to troubleshoot possible error conditions while using the Global LF Inverter & Charger. The following chart is designed to help you quickly pinpoint the most common inverter failures.
AIMS Power Back Feed Short www.aimscorp.net × × Symptom Inverter will not turn on during initial power up. × × × × Possible Cause Batteries are not connected, loose battery-side connections. × × × × Beep continuous Recommended Solution Check the batteries and cable connections. Check DC fuse and breaker. Low battery voltage. No AC output voltage and no indicator lights ON. AC output voltage is low and the inverter turns loads OFF in a short time.
AIMS Power www.aimscorp.net 5 Warranty We offer a 1 year limited warranty. The following cases are not covered under warranty. 1 DC polarity reverse. The inverter is designed without DC polarity reverse protection. A polarity reverse may severely damage the inverter. 2 Wrong AC wiring 3 Operation in a moist environment. 4 Operation with an undersized generator or generator with unqualified wave form.
AIMS Power www.aimscorp.
AIMS Power www.aimscorp.net Remote Control Yes. Optional Input Voltage Waveform Sine wave (Grid or Generator) Nominal Voltage 120Vac 230Vac Low Voltage Trip 80V/90V±4% 184V/154V±4% 90V/100V±4% 194V/164V±4% High Voltage Trip 140V±4% 253V±4% High Voltage re engage 135V±4% 243V±4% Max Input AC Voltage 150VAC 270VAC Bypass & Protection Low Voltage re engage Nominal Input Frequency 50Hz or 60Hz (Auto detect) Narrow: 47±0.3Hz for 50Hz, 57±0.3Hz for 60Hz Low Freq Trip Wide:40±0.