Spec Sheet
SPECIFICATIONS:
Power source: 24V DC. Use two (2) PS-24E.
Current Consumption:
Max. 4A
Capacity: 50 stations. For 80 station capacity, add
NHR-30K Additional Trunk Card.
Talk channel: 1 private channel
Wiring: All wire is twisted, shielded, low
capacitance (12 pF/Ft).
5 twisted pair to NHX-50M Master Station
Aiphone wire #862210
3 twisted pairs to NHR-SP Duty Station
Aiphone wire #862208
3 twisted pairs (plus 1 wire for zone light)
trunkage line to patient stations
Aiphone wire #862208
5 conductors to NHR-3A-4 Zone Light
Aiphone wire #841806
Wiring Distance: 22AWG
65’ to NHX-50M
65’ to NHR-SP
165’ to farthest patient station (ea. trunk)
330’ Max. wire distance per trunk line,
including wire length t-tapped to each
patient station from trunk line.
18AWG
165’ to NHR-3A-4
16’ to PS-24E
Material: High impact ABS fire-retardant plastic
Dimensions
(H x W x D): 18-1/8” x 13-3/8” x 3-7/8”
Certification: UL 1069 Listed
C-UL Canadian Standard C22.2
Product specification subject to change without notice.
ARCHITECTS/ENGINEERS SPECIFICATIONS:
Central Control Unit shall be Aiphone model NHX-
80X, equipped with power switch and concealed
status LED indicators, constructed of high-impact,
fire-retardant ABS plastic.
System capacity shall be 50 call stations, with
expansion capacity to 80 stations with model NHR-
30K additional trunk card, installed inside NHX-80X.
All system functions shall be controlled from NHX-
80X, including call signaling, communication, duty
station, and zone light control. The NHX-80X shall
detect if any patient station becomes disconnected
from the system or if the handset is left off-hook for
more than 90 seconds, and shall send a warning
tone to the master and duty station.
All system wiring shall be terminated inside NHX-
80X with screwless wire connectors. Each trunkage
line from CCU shall contain up to 10 call stations
(NH-1SA, NH-2SA, NHR-3TS), wired in a daisy-
chained fashion. System shall have a maximum of
eight (8) trunkage lines. Master station, duty station,
4-zone indicator light, and power supplies shall be
wired directly to NHX-80X.
Physical size of the CCU shall not exceed 18-1/8” x
13-3/8” x 3-7/8”. NHX-80X shall be mounted on UL
listed 3-gang box or inside UL listed electrical
enclosure. The size of the electrical enclosure shall
be more than 23-3/4” x 19-3/4” x 4”, with a secured
door and a suitable non-combustible mounting
surface inside the enclosure.
Equipment shall be UL 1069 listed, and system
components shall be provided by a manufacturer
having ISO 9001 certification for quality standards.
CONTROLS AND INDICATORS:
• POWER switch
• Under cover:
- System monitoring LEDs (4)
- Reset switch
MOUNTING:
NHX-80X-SS 95363 0797
Printed in USA
Health Care Systems