Installation manual

Split Systems
17
Piping Requirements Allowable Length Details
Maximum
allowable
length
Between outdoor and BP units
Total piping
length
Piping length between outdoor and BP units 180 ft (55 m) -
[Example] a+b+c+d+e 180 ft
Between BP and indoor units
Total piping
length
Piping length between BP and indoor units: 262 ft (80 m) -
[Example] f+g+h+i+j+k+l 262ft
Between BP and indoor unit
1 room
length
Piping length between BP and indoor unit 49 ft (15 m) -
[Example] f, g, h, i, j, k, l 49 ft
Allowable
height
Between outdoor and indoor units
Difference in
height
Difference in height between outdoor and indoor units (H1) 98 ft (30 m)
Between outdoor and BP units Difference in height between outdoor and BP units (H2) 98 ft (30 m)
Between BP and BP units Difference in height between BP and BP units (H3) 49 ft (15 m)
Between indoor and indoor units Difference in height between indoor and indoor units (H4) 49 ft (15 m)
Minimum allowable length Piping length
Pipe length between outdoor unit and first refrigerant branch kit
(refnet joint) 16.4 ft
[Example] a 16.4 ft
Allowable length after the REFNET branch
Piping length from first refrigerant branch kit
(REFNET joint) to indoor unit 131 ft (40 m)
[Example] unit 6: b+c+k 131 ft [Example] unit 5: b+e+j 131 ft
[Example] unit 3: d+h 131 ft
Additional refrigerant calculation
R=
Total length (ft / m)
0.036 lb./ft
(0.054 kg/m)
Total length (ft / m)
of liquid piping size at
x
+
of liquid piping size at
Ø 3/8 inch (Ø 9.5mm) Ø 1/4 inch (Ø 6.4mm)
Superiorflexibilitywithmultizone
customization
Keyfeaturesinclude:
Zonecustomizationwiththeabilitytoconnectfrom
2upto8indoorunitstoasingleoutdoorunit.
Increasedenergysavingswithtechnologically
advancedcomponentsandinvertertechnology.
Superiorflexibilitywiththechoiceofthreeindoor
unittypesforidealcomfortdesignedforanydécor.
Individualzone
controlwithstandardwireless
controls,optionalwiredcontrols,orthe
DaikinENViintelligentthermostat.
RMXS
Outdoor Units – RMXS48LVJU
Model Name
RMXS48LVJU
Nominal Capacity (Cooling / Heating) Btu/h 48,000 / 54,000
SEER / HSPF
Non Ducted 18.8 / 11.3
Mixed 16.5 / 10.5
Ducted 14.1 / 9.6
EER / COP
Non Ducted 10.3 / 3.0
Mixed 9.8 / 2.9
Ducted 9.3 / 2.7
Power Supply 208/230V - 1Ø - 60Hz
Minimum Circuit Amps A 27.0
Maximum Overcurrent Protection A 30.0
Sound Pressure - (Cooling/Heating) dB(A) 56 / 58
Connection Ratio (Max Capacity for BPMKS Boxes)
50 - 130%
Number of Connectable Indoor Units 2 to 8
Number of Connectable BP Units 1 to 3
Total System Piping Length ft. (m) 440 (135)
Piping Connection Kit KHRP26A22T
Operating Range – (Cooling/Heating) °F DB 23 – 115/5 - 75
Dimensions (H x W x D) in.
52-15/16 x 35-7/16 x 12-5/8
Net Weight lbs. 283.0
BP Units
Model Name BPMKS048A2U BPMKS049A3U
Power Supply Single phase 60Hz 208/230V
Power Consumption W 10 10
Running Current A 0.05 0.05
Sound Pressure - (Cooling/Heating) dB(A) 32/32 32/32
Number of Connectable Indoor Units 1 to 2
1 to 3
Min. Connection Combination 7,000 7,000
Max. Connection Combination 48,000
62,000
Piping
Connections
(O.D.)
Liquid
Outdoor Unit Side
in.
Ø 1/4 x 2 Ø 1/4 x 3
Indoor Unit Side
in.
Ø 1/4 x 2 Ø 1/4 x 3
Gas
Outdoor Unit Side
in.
Ø 5/8 x 2 Ø 5/8 x 3
Indoor Unit Side
in.
Ø 5/8 x 2 Ø 5/8 x 3
Dimensions (H x W x D)
in.
7-1/16 x 11-9/16 x 13-3/4
Net Weight
lbs.
18.0 20.0
Nominal Conditions:
Cooling Mode
Indoor: 80 °F DB / 67 °F WB
Outdoor: 95 °F DB
Pipe Length: 25 ft.
Level Difference: 0 ft.
Heating Mode
Indoor: 70 °F DB
Outdoor: 47 °F DB / 43 °F WB
Pipe Length: 25 ft.
Level Difference: 0 ft.
Note:
Specifications are subject to change
without notice
LongerRefrigerantPiping
Longerrefrigerantpipingcapabilitiesoffersmuchmore
flexibilityinthechoiceofinstallationpositionsforthe
indoorunits,andgreatlysimplifiessystemlayout.
BPMKS
BranchPortUnit(BPMKS)
TheBranchPort(BP)unitvariestherefrigerantvolumetomeet
thecoolingorheatingrequirements.It’seasytodisassemble
andmakesrepairsandrecyclingsimple.Choosefrom2zone
or3zoneBPunitstomatchthesystemselectiontoindividual
requirements.