Installation manual

VRV
51
VRV-WIII Unified Heat Pump and Heat Recovery
6 Ton 7 Ton
Model Name RWEYQ72PYDN RWEYQ84PYDN
Performance
Cooling Capacity¹ Btu/h 72,000 84,000
Cooling Input Power kW 4.2 5.6
Heating Capacity² Btu/h 81,000 94,000
Heating Input Power kW 4.0 5.4
Power V/ph/Hz 460/3/60
Sound Pressure Level @ 3ft. dB(A) 50 51
Refrigerant Piping
System Configuration Heat Pump Heat Recovery Heat Pump Heat Recovery
Liquid Pipe (Main Line) in.
3/8 3/8 3/8 3/8
Suction Gas Pipe (Main Line) in.
3/4 3/4 7/8 7/8
Discharge Gas Pipe (Main Line) in.
N/A 5/8 N/A 3/4
Vertical Pipe Length (if unit is below FCU) ft. 164 (130) 164 (130)
Actual Pipe Length (Equivalent Length) ft. 390 (459) 390 (459)
Total Pipe Length ft. 980 980
Connection Ratio
Standard Connectable Indoor Unit Ratio % 50 - 130 50 - 130
Maximum Number of Indoor Units Qty. 12 14
Water Side
(Standard)
BPHE Inlet Pipe (Female Thread) in. 1-1/4 FPT 1-1/4 FPT
BPHE Outlet Pipe (Female Thread) in. 1-1/4 FPT 1-1/4 FPT
Drain Pipe (Female Thread) in. 1/2 FPS 1/2 FPS
Maximum System Water Pressure (BPHE) psi 285 285
Standard Inlet Water Temperature Range °F 50 - 113 50 - 113
Recommended Inlet Water Flow Rate per Module (min.)* gpm 16.4 ~ 39.5 (13.2) 16.4 ~ 39.5 (13.2)
Water Side
(Geothermal)
Inlet Water Temperature Range Cooling** °F 27 (34***) - 113 27 (34***) - 113
Inlet Water Temperature Range Heating °F 14 - 113 14 - 113
Water Flow Rate gpm 21 - 40 21 - 40
Unit
Weight lbs. 330 330
Dimensions (H x W x D) in. 39-3/8 x 30-3/4 x 21-11/16
Electrical
Voltage Range (min - max) V/ph/Hz 414 - 506 414 - 506
Maximum Overcurrent Protection (MOP) A 15 15
Minimum Circuit Amps (MCA) A 10.2 10.2
Compressor Rated Load Amps (RLA) A 5.3 7.0
Compressor
Compressor Type Daikin G-Type Scroll Daikin G-Type Scroll
Compressor Set-Up 1 INV 1 INV
Compressor Capacity Control % 23 - 100 23 - 100
1 Indoor temp. : 80°FDB, 67°FWB/inlet water temp. : 85°F/outlet water temp. : 95°F Equivalent piping length : 25ft, level difference : 0ft.
2 Indoor temp. : 70°FDB, 60°FWB/inlet water temp. : 70°F/Equivalent piping length : 25ft, level difference : 0ft.
* Please note that a water strainer is required for each condensing unit model and now must be field supplied (strainer specification = 50 mesh).
** Application rules apply below 48°F. Please contact your local Daikin office for design assistance and approval.
*** The minimum cooling EWT is 34°F when the condensing unit is located below the indoor units.
Amodular,energysavingandreliablealternativeto
centralizedequipment.
Keyfeaturesinclude:
Compactlightweightcasingat393/8”inheightand
330lbs.inweight
Smallcondenserscanbestackedforreduced
installationspaceandincreasedusablesquare
footage
Largersinglesystemcapacityandmodularconcept
ensureswiderapplicationrange
forsatisfyingfloor
byfloorloadsofcommercialbuildings
AsstandardVRVWIIIcanoperatewithcondenser
watertemperaturesdownto50°Fbutthiscanbe
extendedtoanindustryleading14°Finheating
SingleModuleSystem460V
RWEYQ_PYDN